ASDA-A User Manual
Chapter 5 Trial Run and Tuning Procedure
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
4th Edition 2005/11/30, HE03
5-3
5-2
Applying Power to the Drive
Users please observe the following steps when applying power supply to the servo drive.
1. Please check and confirm the wiring connection between the drive and motor is correct.
1) Terminal U, V, W and FG (frame ground) must connect to Red, White, Black and Green cables
separately (U: Red, V: White, W: Black, FG: Green). If not connect to the specified cable and
terminal, then the drive cannot control motor. The motor grounding lead, FG must connect to
grounding terminal. For more information of cables, please refer to section 3-1.
2) Ensure to connect encoder cable to CN2 connector correctly. If users only desire to execute JOG
operation, it is not necessary to make any connection to CN1 and CN3 connector. For more
information of the connection of CN2 connector, please refer to Section 3-1 and 3-4.
CAUTION
z
Do not connect the AC input power (R, S, T) to the U, V, W output terminals. This
will damage the AC servo drive.
2. Main
circuit
wiring
Connect power to the AC servo. For three-phase input power connection and single-phase input power
connection, please refer to Section 3-1-3.
3. Turn the Power On
The Power includes control circuit power (L1, L2) and main circuit power (R, S, T). When the power is
on, the normal display should be shown as the following figure:
As the default settings of digital input signal, DI6, DI7 and DI8 are Reverse Inhibit Limit (CWL), Forward
Inhibit Limit (CCWL) and Emergency Stop (EMGS) respectively, if need be, the user can change the
settings by using parameters P2-15 to P2-17 freely. When the setting value of parameters P2-15 to
P2-17 is 0, it indicates the function of this DI signal is disabled. For more information of parameters
P2-15 to P2-17, please refer to Chapter 7 “Parameters”.
If the parameter P0-02 is set as motor speed (06), the normal display should be shown as the following
figure:
If there is no text or character displayed on the LED display, please check if the voltage of the control
circuit terminal (L1and L2) is over low.
1) When display shows: