Chapter 7 Parameters
ASDA-A User Manual
4th Edition 2005/11/30,
HE03
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
7-42
3. Users may lock the parameters and protect parameters against change by unauthorized
personnel.
Parameter Lock (Password Input):
Enter 5-digit password (your password should be at least five characters long). Confirm
your password again and then, the password input is completed. (The highest digit of your
password number should be at least set to 1).
Set parameters:
Enter correct password, and then you can unlock the parameters and change them.
Password Decode
First, enter correct password, and set P2-08 to 0(zero) twice continuously.
P2 - 09
DRT
Bounce Filter
Communication Addr.: 0209H
Default: 2
Applicable Control Mode: P/S/T
Range: 0~20
Unit: 2 msec
For example, if P2-09 is set to 5, the bounce filter time is 5 x 2ms=10ms.
When there are too much vibration or noises around environment, increasing the filter time can
improve reliability. However, if the time is too long, it may affect the response time.
P2 - 10
DI1
Digital Input Terminal 1 (DI1)
Communication Addr.: 020AH
Default: 101
Applicable Control Mode: P/S/T
Range: 0~145
Setting:
not used
A
B
C
C=0: normally closed (contact b)
C=1: normally open (contact a)
For the setting value (B, A) of P2-10~P2-17, please refer to Table 7.A.
Please re-start the servo drive after parameters have been changed.
P2 - 11
DI2
Digital Input Terminal 2 (DI2)
Communication Addr.: 020BH
Default: 104
Applicable Control Mode: P/S/T
Range: 0~145
See P2-10 for explanation.