Chapter 5 Trial Run and Tuning Procedure
|
ASDA-AB Series
Revision January 2009
5-11
5.5 Position Trial Run without Load
Before position trial run, fix and secure the motor as possible to avoid the danger from the reacting
force when the motor speed changes.
STEP 1:
Set the value of parameter P1-01 to 01 and it is position (Pr) control mode. After selecting the operation
mode as position (Pr) control mode, please restart the drive and the setting would be valid.
STEP 2:
In position control mode, the necessary DI setting is listed as follows:
Digital Input
Parameter Setting
Value
Sign
Function Description
CN1 PIN No.
DI1 P2-10=101
SON
Servo
On
DI1-=9
DI2 P2-11=108
CTRG Command
trigged DI2-=10
DI3
P2-12=111
POS0
Position command selection
DI3-=34
DI4
P2-13=112
POS1
Position command selection
DI4-=8
DI5 P2-14=102
ARST
Reset
DI5-=33
DI6
P2-15=0
Disabled
This DI function is disabled
-
DI7
P2-16=0
Disabled
This DI function is disabled
-
DI8
P2-17=0
Disabled
This DI function is disabled
-
By default, DI6 is the function of reverse inhibit limit, DI7 is the function of forward inhibit limit and DI6 is the
function of emergency stop (DI8), if the users do not set the setting value of parameters P2-15 to P2-17 to 0
(Disabled), the faults (ALE13, 14 and 15) will occur (For the information of fault messages, please refer to
Chapter 10). Therefore, if the users do not need to use these three digit inputs, please set the setting value
of parameters P2-15 to P2-17 to 0 (Disabled) in advance.
All the digital inputs of Delta ASDA-AB series are user-defined, and the users can set the DI signals freely.
Ensure to refer to the definitions of DI signals before defining them (For the description of DI signals, please
refer to Table 7.A in Chapter 7). If any alarm code displays after the setting is completed, the users can
restart the drive or set DI5 to be activated to clear the fault. Please refer to section 5.2.
For the information of wiring diagram, please refer to Section 3.6.2 (Wiring of position (Pr) control mode).
Because POS2 is not the default DI, the users need to change the value of parameter P2-14 to 113.
Содержание AC Servo Drive ASDA-AB
Страница 1: ......
Страница 13: ...Table of Contents ASDA AB Series Revision January 2009 This page intentionally left blank...
Страница 20: ...Chapter 1 Unpacking Check and Model Explanation ASDA AB Series Revision January 2009 1 7 110V models...
Страница 27: ...Chapter 3 Connections and Wiring ASDA AB Series 3 2 Revision January 2009 Figure 3 2 110V Servo Drive...
Страница 67: ...Chapter 3 Connections and Wiring ASDA AB Series 3 42 Revision January 2009 This page intentionally left blank...
Страница 85: ...Chapter 5 Trial Run and Tuning Procedure ASDA AB Series 5 8 Revision January 2009...
Страница 103: ...Chapter 5 Trial Run and Tuning Procedure ASDA AB Series 5 26 Revision January 2009 This page intentionally left blank...
Страница 149: ...Chapter 6 Control Modes of Operation ASDA AB Series 6 46 Revision January 2009 This page intentionally left blank...
Страница 246: ...Chapter 8 MODBUS Communications ASDA AB Series Revision January 2009 8 3 Cable Connection...
Страница 265: ...Chapter 9 Maintenance and Inspection ASDA AB Series 9 4 Revision January 2009 This page intentionally left blank...
Страница 275: ...Chapter 10 Troubleshooting ASDA AB Series 10 10 Revision January 2009 This page intentionally left blank...
Страница 282: ...Chapter 11 Specifications ASDA AB Series Revision January 2009 11 7 11 3 Servo Motor Speed Torque Curves...
Страница 307: ...Chapter 12 Application Examples ASDA AB Series 12 10 Revision January 2009...
Страница 333: ...Chapter 12 Application Examples ASDA AB Series 12 36 Revision January 2009 8 B A 2 5 Position SPEED Z pulse...
Страница 335: ...Chapter 12 Application Examples ASDA AB Series 12 38 Revision January 2009 Connecting to Delta DVP 01PU...
Страница 336: ...Chapter 12 Application Examples ASDA AB Series Revision January 2009 12 39 Connecting to Mitsubishi FX1PG...
Страница 337: ...Chapter 12 Application Examples ASDA AB Series 12 40 Revision January 2009 Connecting to Mitsubishi FX2N1PG...
Страница 338: ...Chapter 12 Application Examples ASDA AB Series Revision January 2009 12 41 Connecting to Mitsubishi AD75...
Страница 339: ...Chapter 12 Application Examples ASDA AB Series 12 42 Revision January 2009 This page intentionally left blank...
Страница 353: ...Appendix A Accessories ASDA AB Series A 14 Revision January 2009 This page intentionally left blank...
Страница 356: ...Appendix A Accessories ASDA AB Series Revision January 2009 B 3 Figure 1 Saddle on both ends Saddle on one end Figure 2...