Figure 61. Removing an FCM (1 of 2)
Figure 62. Removing an FCM (2 of 2)
NOTE:
The FCM slot must not be empty for more than 2 minutes while the enclosure is powered.
Installing an FCM
1
You can hotswap the replacement of a single FCM; however, if replacing multiple FCMs, the enclosure must be powered off using an
orderly shutdown using the management interfaces.
2
Orient the FCM for insertion into the target slot on the enclosure rear panel, as shown in
Figure 62. Removing an FCM (2 of 2)
3
Slide the FCM into the slot until the latch clicks home.
The enclosure should automatically detect and make use of the new module.
4
Wait for the Module OK LED on the newly inserted FCM to illuminate green. See
Figure 26. Fan cooling module (FCM)
.
•
If the Module OK LED does not illuminate, verify that the FCM is properly inserted and seated in the slot.
•
If properly seated, the module may be defective. Check the ME Storage Manager and the event logs for more information.
•
Using the management interfaces (the ME Storage Manager or CLI), determine if the health of the new FCM is OK. Verify that
the Module OK LED is green, and that the Ops panel states show no amber module faults.
5
If replacing multiple FCMs, repeat steps 1 through 4.
74
Module removal and replacement