4.8.6 CRANKING
Crank disconnect settings are used to detect when the set fires during the starting sequence.
As the set is cranked, the first parameter that passes it’s
crank disconnect
setting will result in the cessation of
the cranking signal.
Having more than one
crank disconnect
source allows for a much faster crank disconnect response leading to
less wear on the engine and starter components, and provides added safety in case one source is lost, by a
blown or tripped fuse for example.
Click and drag to change the
setting.
Type the value
or click the up
and down
arrows to
change the
settings
If
check oil pressure prior to
starting
is enabled, the cranking
will not be allowed if the oil
pressure is not seen as being
low. This used as a
double check
that the engine is stopped before
the starter is engaged
When enabled, releasing the start
button during a manual start will also
disconnect the crank.
Manual Crank Limit is provided to
protect the engine from being
cranked too long in case of a start
failure.
Содержание DSE8810
Страница 117: ...Edit Configuration 117 Actions Drive a PLC function Write a value to a Gencomm register Reset an alarm ...
Страница 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Страница 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Страница 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Страница 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...
Страница 148: ...This Page Is Intentionally Left Blank 148 ...