Edit Configuration
111
4.14.2.5 PLC FUNCTIONS
PLC Functions allow the PLC logic to create alarm conditions or drive ‘virtual inputs’ on the controller.
A PLC function is configured in the same way as a module digital input:
Predefined Functions
Predefined functions can only be used once in the DSE Configuration Suite. For example if digital input A is
configured to ‘remote start on load’, another input cannot be configured to the same function. Similarly, a PLC
function cannot be configured to this function either.
Where this is a required function, it is achieved by setting the digital input to “User Configured”, “always
active”, “indication”, and OR’ing this into the PLC condition as follows:
Function. See section entitled
Input functions
for details of all
available functions
As this example shows a
predefined
function,
these parameters are
greyed out
as they are
not applicable
Condition: Battery Volts below 10V
OR Digital input A is active.
Action: Trigger PLC Function 1(Remote Start On Load)
Содержание DSE8810
Страница 117: ...Edit Configuration 117 Actions Drive a PLC function Write a value to a Gencomm register Reset an alarm ...
Страница 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Страница 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Страница 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Страница 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...
Страница 148: ...This Page Is Intentionally Left Blank 148 ...