Edit Configuration
24
Function
Description
Droop enable
This input is used to switch the engine into droop mode on CAN
engines that support this function.
Duty Select
IEEE 37.2 - 10 Unit sequence
switch
This input is used to force the appropriate set to become the duty set
when using a load demand scheme. Irrespective of the priority number
configured in the module, it will be forced to become the priority set.
This allows for manual duty selection, overriding the automatic system
normally used by the modules.
EJP1
For the French EJP (Effacement Jours de Pointe) tarrif system.
This input is functionally identical to
Remote Start Off Load.
If this input is active, operation will be similar to the ‘Remote Start on
load’ function except that the generator will not be instructed to take the
load. This function can be used where an engine only run is required
e.g. for exercise.
EJP2
For the French EJP (Effacement Jours de Pointe) tarrif system.
This input is functionally identical to
Remote Start On Load.
When in auto mode, the module will perform the start sequence and
transfer load to the generator.
If in Manual mode, the load will be transferred to the generator if the
engine is already running, however in manual mode, this input will not
generate start/stop requests of the engine.
In both cases, synchronising takes place if required.
External Panel Lock
This input is used to provide security to the installation. If the External
Panel lock input is active, the module will not respond to operation of
the Mode select or start buttons. This allows the module to be placed
into a specific mode (such as Auto) and then secured. The operation of
the module is not affected and the operator will still be able to view the
various instrumentation pages etc. (
Front panel configuration access is
still possible while the system lock is active
).
NOTE: External control sources (i.e. Simulate Start Button)
are not affected by the external panel lock input and will continue
to operate normally.
Generator Closed Auxiliary
IEEE 37.2 - 3 Checking or
interlocking relay
This input is used to provide feedback to allow the controller to give true
indication of the contactor or circuit breaker switching status. It should
be connected to the generator load switching device auxiliary contact.
Action:
Warning
(Alarm only, No shutdown)
Generator Load Inhibit
IEEE 37.2 - 52 AC circuit breaker
This input is used to prevent the module from loading the generator. If
the generator is already on load, activating this input will cause the
module to unload the generator. Removing the input will allow the
generator to be loaded again.
NOTE: This input only operates to control the generator-
switching device if the module load switching logic is attempting
to load the generator. It will not control the generator-switching
device when the mains supply is on load.
High Coolant Temperature
Electrical Trip
A digital normally open or closed coolant temperature switch gives this
input. It allows high coolant temperature detection using the switch and
the analogue input to be used in parallel to give protection. Upon
activation of the input an electrical trip alarm is generated.
Inhibit Scheduled Run
IEEE 37.2 - 3 checking or
interlocking relay
This input is used to provide a means of disabling a scheduled run.
Inhibit SMS Remote Start
This input is used to inhibit the module from starting the generator when
a remote start signal is received by SMS.
Lamp Test
This input is used to provide a test facility for the front panel indicators
fitted to the module. When the input is activated all LED’s should
illuminate.
Load Share Inhibit
When active, this input disables the VAr share control when in parallel
Содержание DSE8810
Страница 117: ...Edit Configuration 117 Actions Drive a PLC function Write a value to a Gencomm register Reset an alarm ...
Страница 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Страница 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Страница 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Страница 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...
Страница 148: ...This Page Is Intentionally Left Blank 148 ...