Edit Configuration
106
4.14.1 ADVANCED OPTIONS
4.14.1.1 PROTECTIONS
This feature is provided to assist the system designer in meeting specifications for “Warning only”,
“Protections Disabled”, “Run to Destruction”, “War mode” or other similar wording.
WARNING! Enabling this feature will prevent the set being stopped upon critical alarm
conditions. All shutdown alarms are disabled with the exception of EMERGENCY STOP which
continues to operate.
Options
Description
Disable
= The module will operate as normal and provide engine shutdown if required.
=
Protections disabled
function is activated. Operation depends upon the following
configuration.
NOTE: Writing a configuration to the controller that has “Protections Disabled”
configured, results in a warning message appearing on the PC screen for the user to
acknowledge before the controller’s configuration is changed. This prevents
inadvertent activation of the feature.
Protections are
disabled
Never
: The protections are not disabled
Always
: Protections are always overridden by the DSE controller.
On Input
: Protections are disabled whenever a configurable input set to
Protections
Disabled
is activated
Protections
Disabled Alarm
Action
If
Disable All Protections
is set to
On Input
, this selection allows configuration of an alarm to
highlight that the protections have been disabled on the engine.
Indication:
Any output or LCD display indicator configured to
Protections Disabled
will be
made active; however the internal alarm sound will not operate.
Warning
:
Any output or LCD display indicator configured to
Protections Disabled
will be
made active, and the internal alarm sound will operate.
When protections are disabled,
Protections Disabled
will appear on the module display to
inform the operator of this status.
Coolant Level
Protection
Override
= When a CANbus engine is selected, the
Coolant Level Protection
is provided when
supported by the ECU.
= The
Coolant Level Protection
is overridden and does not activate an alarm on the
module.
Содержание DSE8810
Страница 117: ...Edit Configuration 117 Actions Drive a PLC function Write a value to a Gencomm register Reset an alarm ...
Страница 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Страница 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Страница 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Страница 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...
Страница 148: ...This Page Is Intentionally Left Blank 148 ...