Edit Configuration
36
Output source
Activates…
Is not active….
Remote Start Off Load
This output indicates that a digital input that has been configured as ‘
Remote
Start off load
’ is active. This output could be used to pass the remote start
signal on to elsewhere in the control system.
Remote Start On Load
This output indicates that a digital input that has been configured as ‘
Remote
Start on load
’ is active. This output could be used to pass the remote start
signal on to elsewhere in the control system.
Remote Start On Load Demand
Indicates that the module’s input is active for remote start on load demand.
Also indicates that the controller has received a remote start on load signal
from the 8860 via the MSC link.
Remote Start Over MSC
Indicates that the controller has received a remote start on load signal from the
8860 via the MSC link.
Reset Maintenance Alarm 1, 2, 3
Active when a digital input
Reset Maintenance Alarm 1, 2, 3
is active
Reset Governor to Datum
This output is intended to be used in conjunction with an electronic or
motorised potentiometer, which has a ‘centre pot’ type input. This output is
activated whenever the module needs to reset the potentiometer to its centre
position.
Reset AVR to Datum
This output is intended to be used in conjunction with an electronic or
motorised potentiometer, which has a ‘centre pot’ type input. This output is
activated whenever the module needs to reset the potentiometer to its centre
position.
Return delay in progress
This output source will be active to indicate that the return timer is running.
Right Button Pressed
Active when the Right button on the
front fascia is pressed
Inactive when the button is released
Short Circuit Generator
This output indicates that the module has detected a short circuit on the
generator output.
Shutdown Blocked
Indicates that a
Shutdown
type alarm is active but that the shutdown function
has been blocked because the
Protections Disabled
function is active.
Simulate Auto Button
Active when a digital input configured to
Simulate Auto Button
is active
Simulate Lamp Test / Mute
Active when a digital input configured to
Simulate Lamp Test / Mute
is active
Simulate Manual Button
Active when a digital input configured to
Simulate Manual Button
is active
Simulate Start Button
Active when a digital input configured to
Simulate Start Button
is active
Simulate Stop Button
Active when a digital input configured to
Simulate Stop Button
is active
Simulate Test On Load Button
Active when a digital input configured to
Simulate Test On Load Button
is
active
Simulate Transfer To Generator
Button
Active when a digital input configured to
Simulate Transfer To Generator
Button
is active
Simulate Transfer To Mains
Button
Active when a digital input configured to
Simulate Transfer To Mains Button
is
active
Smoke Limiting
Becomes active when the controller
requests that the engine runs at idle
speed.
As an output, this can be used to
give a signal to the
Idle input
of an
engine speed governor (if available)
Becomes inactive when the controller
requests that the engine runs at rated
speed.
SMS Remote Start Off Load
Active when the module receives a remote start off load command by SMS
SMS Remote Start On Load
Active when the module receives a remote start on load command by SMS
Speed Lower Relay
This output will be used to give a speed lower signal to the external governor
or electronic pot.
Speed Raise Relay
This output will be used to give a speed raise signal to the external governor
or electronic pot.
Start Delay in Progress
This output source will be active to indicate that the module’s internal start
delay timer is running. Once this timer expires the module with initiate its start
sequence.
Start Relay
IEEE 37.2 – 54 turning gear engaging
device
Active when the controller requires the cranking of the engine.
Содержание DSE8810
Страница 117: ...Edit Configuration 117 Actions Drive a PLC function Write a value to a Gencomm register Reset an alarm ...
Страница 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Страница 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Страница 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Страница 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...
Страница 148: ...This Page Is Intentionally Left Blank 148 ...