4.14.2.9 EXAMPLES
AUTO MUTE after 30 seconds and provide a manual mute function using Digital Input C.
Condition
Action
Flag Test
(Audible Alarm)
Start Timer 1
(30 seconds)
If the audible alarm is active
Begin a 30 second delay
Condition
Action
Timer 1 expired
OR
Flag Test
(Digital Input C)
Trigger Function
(
Alarm Mute)
When the timer expires OR
Digital Input C is activated
Trigger the alarm mute
function
PLC Function 1 configured to
Alarm Mute.
Digital Input C configured to
Indication. This input will be
checked for by the PLC logic.
Descriptive text placed in the
“LCD Display” box for future
reference.
(LCD Display text does not appear
on the screen for “indication” inputs).