Edit Configuration
26
Function
Description
Simulate Lamp test \ Alarm
Mute Button
This input is used to provide a test facility for the front panel indicators
fitted to the module. When the input is activated all LED’s should
illuminate. The input also serves a second function, in that it also
provides a mute signal to silence the audible alarm. The input is
recognised by the module as though it was the Push button on the
module itself being operated.
Simulate Manual Button
This input mimic’s the operation of the ‘Manual’ button and is used to
provide a remotely located Manual mode push button.
Simulate Start Button
This input mimic’s the operation of the ‘Start’ button and is used to
provide a remotely located start push button.
Simulate Stop Button
This input mimic’s the operation of the ‘Stop’ button and is used to
provide a remotely located stop/reset push button.
Smoke limit
IEEE 37.2 – 18 accelerating or
decelerating device
This input instructs the module to give a
run at idle speed
command to
the engine either via an output configured to
smoke limit
or by data
commands when used with supported electronic engines.
Speed Lower
On systems where internal relays are used to control the governor, this
input can be used to decrease the speed.
NOTE: This input has no effect when utilising the internal
analogue system to control the governor.
Speed Raise
On systems where internal relays are used to control the governor, this
input can be used to increase the speed.
NOTE: This input has no effect when utilising the internal
analogue to control the governor.
Start Pause
IEEE 37.2 - 3 checking or
interlocking relay
This input is intended to be used to allow the generator start sequence
to commence, but not to complete. This feature can be used with Air
start engines for example to give a controlled start sequence.
The function operates such that if the ‘Start pause’ input is active and
an engine start is commanded, the module will perform its start
sequence thus: -
The pre-heat output (if used) will be activated for the duration of the pre-
heat timer.
The Fuel output will then be energised and the module will then enter a
pause state - ‘Awaiting clear to start’. If the ‘start pause’ signal becomes
inactive at this time then the module will continue its normal start
sequence.
The ‘start pause’ mode uses the ‘manual crank limit’ timer and if this
expires during the ‘Awaiting clear to start’ state then a ‘Fail to start’
alarm will be generated and the set shutdown.
Stop and Panel Lock
Combined function input that instructs the module to enter
STOP
MODE
and also perform the
Panel Lock
function.
Once the input is active, the module will not respond to operation of the
Mode select or start buttons.
The operator will still be able to view the various instrumentation pages
etc. (
Front panel configuration access is still possible while the system
lock is active
).
Volts Raise
On systems where internal relays are used to control the AVR, this
input can be used to increase the volts.
NOTE: This input has no effect when utilising the internal
analogue system to control the AVR
Volts Lower
On systems where internal relays are used to control the AVR, this
input can be used to decrease the volts.
NOTE: This input has no effect when utilising the internal
analogue system to control the AVR
Содержание DSE8810
Страница 117: ...Edit Configuration 117 Actions Drive a PLC function Write a value to a Gencomm register Reset an alarm ...
Страница 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Страница 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Страница 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Страница 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...
Страница 148: ...This Page Is Intentionally Left Blank 148 ...