Edit Configuration
38
Output source
Activates…
Is not active….
Voltage Lower Relay
Used when the
internal relays
scheme of AVR control is used. This output can
be used to drive a motorised potentiometer or Voltage Lower input of an AVR
Voltage Raise Relay
Used when the
internal relays
scheme of AVR control is used. This output can
be used to drive a motorised potentiometer or Voltage Raise input of an AVR
Waiting for generator
This output indicates that the engine has been instructed to start but has not
yet become available. Once the generator becomes available this output will
become in-active. (Available = Generator Frequency and Voltage levels are
above the ‘
Loading
’ levels set in the configuration)