Edit Configuration
64
LOAD OPTIONS
Item
Function
Load Control Mode
IEEE 37.2 -90 Regulating device
Disabled:
No load sharing will take place.
Load Share (DSE8810 only):
The load will be shared between all the sets
in the system.
KW fixed export:
The generator will export a fixed amount of active (kW)
power.
NOTE: On model DSE8810 kW fixed export is only used in
conjunction with generating sets in parallel with the mains supply.
NOTE: The DSE8810 will automatically switch from load share
mode to kW fixed export mode when an input configured for
Mains
parallel mode
is active.
Reactive load control mode
IEEE 37.2 -90 Regulating device
Not available when Active (kW) load share mode is set to
Disabled
.
Options:
Disabled:
No reactive power (VAr/pf) sharing will take place.
VAr Share:
Reactive power (VAr) will be shared between all the sets in the
system.
VAr fixed export:
The generator will produce a fixed amount of reactive
power (VAr) for use when in parallel with the mains supply.
NOTE: The DSE8810 will automatically switch from VAr share
mode to VAr fixed export mode when an input configured for
Mains
parallel mode
is active.
RAMP
Item
Function
Ramp Speed
The rate at which the generator will be ramped onto and off the load.
NOTE: The set will initially take load at the level set by load ramp
minimum and will then increase it’s load share at this rate until either:
•
All the sets have an equal share of the load (DSE8810 module only)
•
The generated power is equal to the setting for ‘load parallel
power’
When the set is unloaded it will ramp down at this rate from the current
load level to the level set by load parallel ramp minimum before being
removed from the bus (or mains supply).
Содержание DSE8810
Страница 117: ...Edit Configuration 117 Actions Drive a PLC function Write a value to a Gencomm register Reset an alarm ...
Страница 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Страница 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Страница 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Страница 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...
Страница 148: ...This Page Is Intentionally Left Blank 148 ...