Edit Configuration
60
AVR
IEEE 37.2 -90 regulating device
These settings configure the method of interface between the DSE controller and the Automatic
Voltage Regulator (AVR)
Parameter
Description
AVR Interface
None –
No external interface is fitted between the controller and the
AVR and no control over voltage matching or VAr sharing will be made.
Internal Relays
– The AVR or motorised potentiometer is controlled by
the DSE8810 modules own internal relays.
NOTE: It will be necessary to configure two of the module
relays to provide the required ‘Voltage raise’ and ‘Voltage Lower’
signals.
Internal Analogue -
This external interface is used to provide a DC
voltage output to interface with many AVRs remote voltage adjust or
load sharing controller inputs.
AVR Output Reversed
Only available in conjunction with internal analogue selected
This allows the module to interface with a greater diversity of
AVRs.
= Lower voltage equates to lower voltage.
= Lower voltage equates to higher voltage.
Adjust to nominal voltage
This option determines the action that will be taken by the
synchroniser during the period that the set is running on load.
Adjust to Centre Point –
Whenever generators are required to run in
parallel, then active load sharing is recommended. However, this may
not be essential when the accuracy of the load sharing is not critical and
is only required for short periods. In this case ‘droop’ AVRs must be
used in conjunction with the ‘synchronising reset option – reset to datum
on load’ feature. This works on the principal that the governed voltage of
each generator for any given load will be the same when at its datum
setting. This approach is generally unsuitable for mains connected
systems but will provide rudimentary load sharing between two or more
generators.
Adjust to Nominal –
When on load as a single set (but not in parallel)
the load sharing module will effect changes to the AVR to keep the
system voltage at nominal levels. These levels are user adjustable on
the ‘generator’ tab accessible via Config Suite PC software.
This is used to ensure the nominal voltage of the system is maintained
even if droop is configured.
None –
Adjustment will not take place; the speed and voltage will
remain at current levels.
When in parallel with other sets, the DSE load share controller will
automatically keep the system voltage at nominal levels regardless of
the selection of this parameter.
Содержание DSE8810
Страница 117: ...Edit Configuration 117 Actions Drive a PLC function Write a value to a Gencomm register Reset an alarm ...
Страница 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Страница 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Страница 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Страница 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...
Страница 148: ...This Page Is Intentionally Left Blank 148 ...