Edit Configuration
13
4.3.1 ECU (ECM) OPTIONS
Parameter
Description
Engine type
Select the engine type appropriate to your system
Conventional Engine:
Select this if you have a traditional (non ECU) engine, either Energise
to Run or Energise to Stop.
Conventional Gas Engine:
Select this if you have a traditional (non ECU) engine and require
GAS engine functionality. This enables control of configurable outputs for
Gas Choke and
Gas Ignition
and instructs the module to follow the gas engine timers.
Other Engines:
The list of supported CAN (or Modbus) engines is constantly updated, check
the DSE website at
www.deepseaplc.com
for the latest version of Configuration Suite
software.
Enhanced J1939
= The module will read ‘Basic’ instrumentation from the engine ECU and display (where
supported by the engine) :
•
Engine Speed
•
Oil Pressure
•
Engine Coolant Temperature
•
Hours Run
= The module will read and display an ‘Enhanced’ instrumentation list (where supported
by the engine) :
•
Engine Speed
•
Oil Pressure
•
Engine Coolant Temperature
•
Hours Run
•
Engine Oil Temperature
•
Exhaust Temperature
•
Fuel Pressure
•
Total Fuel used
•
Fuel Consumption
•
Inlet Manifold Temperature
•
Coolant Pressure
•
Turbo Pressure
Where an instrument is not supported by the engine ECU, the instrument is not displayed.
DSE Reserve the right to change these lists in keeping with our policy of continual
development.
Alternative
Engine Speed
= The engine is instructed to run at its
Nominal Speed
as configured by the Engine
Manufacturer.
= The engine is instructed to run at its
Alternative Speed
as configured by the Engine
Manufacturer.
Modbus Engine
Comms Port
RS485 Port:
The modules RS485 port is used to communicate to the engine (when a
Modbus engine type is selected.
DSENet Port:
The modules DSENet port is used to communicate to the engine (when a
Modbus engine type is selected. This ‘frees’ the RS485 port in case connection to BMS or
other RS485 compatible equipment is required.
Содержание DSE8810
Страница 117: ...Edit Configuration 117 Actions Drive a PLC function Write a value to a Gencomm register Reset an alarm ...
Страница 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Страница 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Страница 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Страница 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...
Страница 148: ...This Page Is Intentionally Left Blank 148 ...