DKM-409 Pro AT User Manual Rev_02 Firmware V-2.5
K91D01-EN - 43 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Reactive Power
Capacitive Alarm
kVAr
0
9999
0
If the reactive power of any channel is
capacitive and goes above this limit,
this will cause an alarm.
If this limit is 0 then the alarm is not
controlled.
Reactive Power Inductive
Alarm
kVAr
0
9999
0
If the reactive power of any channel is
inductive and goes above this limit, this
will cause an alarm.
If this limit is 0 then the alarm is not
controlled.
Reactive Power Alarm
Duration
sec
0
255
30
If the reactive power of any channel
goes outside of the limits during this
timer, a reactive power alarm will occur.
Reactive Power Alarm
Lock Enable
-
0
1
1
0: alarm non latching
1: latching alarm
Power Factor Capacitive
Alarm
-
0.000
1.000
0.000
If the power factor of any channel is
capacitive and goes below this limit, this
will cause an alarm.
If this limit is 0 then the alarm is not
controlled.
Power Factor Inductive
Alarm
-
0.000
1.000
0.000
If the power factor of any channel is
inductive and goes below this limit, this
will cause an alarm.
If this limit is 0 then the alarm is not
controlled.
Power Factor Alarm
Duration
sec
0
255
30
If the power factor of any channel goes
outside of the limits during this timer, a
power factor alarm will occur.
Current High Alarm
A
0
25000
0
If the current of any phase goes above
this limit, this will cause an alarm.
If this limit is 0 then high current alarm
is not controlled.
Current Alarm Duration
sec
0
255
30
If the current goes above the limit
during this timer, a current alarm will
occur.
Current Alarm Lock
Enable
-
0
1
1
0: alarm non latching
1: latching alarm
THD-V Alarm
%
0
50
0
If the THD of any voltage channel goes
above this limit, this will cause an alarm.
If this limit is 0 then the alarm is not
controlled.
THD-V Alarm Duration
sec
0
255
30
If the THD of any voltage channel goes
above the limit during this timer, a THD-
V alarm will occur.
THD-V Alarm Lock
Enable
-
0
1
1
0: alarm non latching
1: latching alarm
THD-I Alarm
%
0
50
0
If the THD of any current channel goes
above this limit, this will cause an alarm.
If this limit is 0 then the alarm is not
controlled.
THD-I Alarm Duration
sec
0
255
30
If the THD of any current channel goes
outside of the limits during this timer, a
THD-I alarm will occur.
THD-I Alarm Lock
Enable
-
0
1
1
0: alarm non latching
1: latching alarm
Содержание DKM-409 PRO AT
Страница 20: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 2 3 PHASE 4 WIRE STAR 4 3 3 PHASE 3 WIRE DELTA ...
Страница 21: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 23: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 8 1 PHASE 2 WIRE ...
Страница 24: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 5 CONNECTION DIAGRAM ...