DKM-409 Pro AT User Manual Rev_02 Firmware V-2.5
Supply voltage operating
limits:
STANDARD AC SUPPLY VERSIONS:
100-265VAC
(±%15), 50-
60Hz
(±%10), 88-400VDC
OPTIONAL DC SUPPLY VERSIONS:
19-150VDC
Reverse voltage:
Non polarized inputs, works in both polarizations.
Maximum input power:
15 VA
Isolation
3500VAC/1minute from all other terminals.
Measurement method:
True RMS
Sampling rate:
8192 samples/sec.
Harmonic analysis:
up to 49th harmonic
Input voltage range:
0 to 300 VAC (phase-neutral)
Measurement range:
7 to 330VAC ph-N (14 to 520VAC ph-ph)
Input impedance:
4.5M-ohms
Display resolution:
0.1VAC
Accuracy:
0.5% + 1 digit @ 230VAC ph-
N (±2VAC ph-N)
0.5% + 1 digit @ 400VAC ph-
ph (±3VAC ph-ph)
Withstanding:
1300V-AC continuous
Frequency range:
30 to 100 Hz
Frequency display
resolution:
0.01 Hz
Frequency accuracy:
0.5% + 1 digit
3. TERMINAL DESCRIPTIONS
3.1. AUXILIARY SUPPLY INPUT
The connection cables for the power supply voltage
must be fused with a UL listed fuse (6A type C).
3.2. AC VOLTAGE INPUTS
Power Supply
Connector