EFFECT OF PHASE SWAPPING
The network is still loaded with 100 kW on each phase. The load Power Factor (PF) is 1.
PF in phases L2 and L3 will show -0,50 due to phase shift between voltages and currents which is caused
by CT swapping. The result is that total network power displayed by controller is 0 kW.
Measured values are as follows:
kW
kVAr
kVA
pf
Phase L1
100.0
0.0
100
1.00
Phase L2
-50.0
86.6
100
-0.50
Phase L3
-50.0
-86.6
100
-0.50
Total
0.0
0.0
300
0.0
Number of inputs:
4 inputs, all configurable
Input type:
Opto-isolated digital input
Function selection:
From list
Contact type:
Normally open or normally closed (programmable)
Minimum pulse duration:
250ms
Active level:
40-135V-DC or 30-265V-AC
Isolation:
1000VAC, 1 minute
Noise filtering:
Yes
3.4. DIGITAL INPUTS