DKM-409 Pro AT User Manual Rev_02 Firmware V-2.5
K91D01-EN - 36 -
The unit features more than 400 event logs with date-time stamp and full snapshot of measured values
at the moment that the event has occurred.
Stored values in an event record are listed below:
-event number
-event type / fault definition (see below for various event sources)
-date and time
-binary values of all alarm, input and output bits.
-Ph-N voltages: V1-V2-V3
-Ph-Ph voltages: U12-U23-U31
-Phase currents: I1-I2-I3
-frequency
-total active power (kW)
-total reactive power (kVAr)
-total apparent power (kVA)
-total power factor
-Total harmonic distortion: V1-V2-V3-U12-U23-U31-I1-I2-I3
Possible event sources are various. Every source can be individually enabled or disabled:
Alarm events:
recorded when the related fault condition occurs.
Warning events:
recorded when the related warning condition occurs.
Input events:
recorded when the status of a digital input is changed.
Programming event:
Recorded with the password level when program mode is entered.
Reset event:
recorded when device reset.
Output event:
recorded when the status of a digital output changes.
Periodic event:
records measurements and parameters with specified time periods.
16. DISPLAYING EVENT LOGS
Event enable
selection tabs
Содержание DKM-409 PRO AT
Страница 20: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 2 3 PHASE 4 WIRE STAR 4 3 3 PHASE 3 WIRE DELTA ...
Страница 21: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 23: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 8 1 PHASE 2 WIRE ...
Страница 24: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 5 CONNECTION DIAGRAM ...