DKM-409 Pro AT User Manual Rev_02 Firmware V-2.5
K91D01-EN - 57 -
REGISTER
ADDRES
VARIABLE
DESCRIPTION
LENGHT
R/W
TYPE
X
16384
Password
Programming Password
16 BIT
W-O Unsigned
word
x1
16385
Button
Button Simulation
BIT0: Set
BIT1: Up Arrow
BIT2: Down Arrow
16 BIT
W-O Unsigned
word
x1
16386
Factory
Return to factory settings
16 BIT
W-O Unsigned
word
x1
16387
Counter
Reset
Reset All Counters
16 BIT
W-O Unsigned
word
x1
16388
Read_Flsh Write on internal flash memory
16 BIT
W-O Unsigned
word
x1
16389
Read_Rec
Copy record to the BUFFER
16 BIT
W-O
Unsigned
Word
x1
16390
BOOT
BOOT JUMP
16 BIT
W-O
Unsigned
Word
x1
16391
Relay
Remote control relay func. Write
16 BIT
W-O Unsigned
word
x1
REGISTER
ADDRES
VARIABLE
DESCRIPTION
LENGHT
R/W
TYPE
X
8192
Year
Year (0-4096)
16 BIT
R/W Unsigned
word
x1
8193
Month
Month (1-12)
16 BIT
R/W Unsigned
word
x1
8194
Day_Month Day (1-31)
16 BIT
R/W Unsigned
word
x1
8196
Hour
Hour (0-23)
16 BIT
R/W Unsigned
word
x1
8197
Minute
Minute (0-59)
16 BIT
R/W Unsigned
word
x1
8198
Second
Second (0-59)
16 BIT
R/W Unsigned
word
x1
8199
Latitude
Latitude (+- 66.499) Negative latitude
means “South”
32 BIT
R-O Signed
long
x1000
8201
Longitude
Longitude (+- 179.999) Negative
longitude means “West”
32 BIT
R-O Signed
long
x1000
21.7. COMMANDS
21.8. REAL TIME CLOCK
Содержание DKM-409 PRO AT
Страница 20: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 2 3 PHASE 4 WIRE STAR 4 3 3 PHASE 3 WIRE DELTA ...
Страница 21: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 23: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 8 1 PHASE 2 WIRE ...
Страница 24: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 5 CONNECTION DIAGRAM ...