DKM-409 Pro AT User Manual Rev_02 Firmware V-2.5
Supply Input:
100-265V AC
(±15%), 50/60Hz (±10%),
88-400V DC
Measurement Inputs:
Voltage:
7 - 300 V AC (P-N)
14 - 520 V AC (P-P)
Current:
0.001
– 6.00 A AC
Frequency:
30 - 100 Hz
Accuracy:
Voltage:
0.5% + 1 digit
Current:
0.5% + 1 digit
Frequency:
0.5% + 1 digit
Power
(kW,kVAr)
:
1.0% + 2 digit
Cos:
0.5% + 1 digit
Withstanding:
Current:
100 A AC during 1 sec.
Voltage:
1300 V AC (continuous)
Analog Outputs:
Active 4-20mA
Precision:
16 bit
Measurement Range:
CT range:
5/5A to 25000/5A
VT range:
0.1
/
1 to 5000.0
/
1
kW range:
1.0 kW to 5000 MW
Power Consumption:
< 15 VA
Voltage Burden:
< 0.02VA per phase
Current Burden:
< 0.5VA per phase
Relay Outputs:
5A @ 250V AC
Digital Inputs:
Active level:
40 to 135V DC or 30 to 265V AC
Min pulse:
250ms.
Isolation:
1000V AC, 1 minute
Serial Port:
Signal level:
RS-485
Protocol:
Modbus RTU
Data Rate:
Adjustable 2400-115200 bauds
İsolation:
500V AC, 1 minute
Operating Temp. Range:
-
20°C to +70 °C (-4°F to 158°F)
Max Humidity:
95%, non-condensing
Degree of Protection:
IP 54 (Front Panel)
IP 30 (Back Panel)
Enclosue:
Non-flammable, ROHS compliant
Installation:
Flush mounting with rear brackets
Dimensions:
102x102x53mm (WxHxD)
Panel Cutout:
92x92mm
Weight:
200 gr
EU Directives:
2006/95/EC (LVD)
2004/108/EC (EMC)
Norms of Reference:
EN 61010 (safety)
EN 61326 (EMC)
UL-CSA Certification:
UL 61010-1, 3rd Edition, 2012-05,
CAN/CSA-C22.2
File: E475547, Vol. D1
6. TECHNICAL SPECIFICATIONS
Содержание DKM-409 PRO AT
Страница 20: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 2 3 PHASE 4 WIRE STAR 4 3 3 PHASE 3 WIRE DELTA ...
Страница 21: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 23: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 8 1 PHASE 2 WIRE ...