DKM-409 Pro AT User Manual Rev_02 Firmware V-2.5
K91D01-EN - 53 -
BYTE DESCRIPTION
VALUE
0
Controller
Address
1-253
1
Function Code
3
2
Starting Address
(Upper)
See below for detailed explanation
3
Starting Address
(Lower)
See below for detailed explanation
4
Register Number
(Upper)
0
5
Register Number
(Lower)
Max 7Bh (123 decimal)
6
CRC Lower Byte CRC calculation is mentioned below
7
CRC Upper Byte CRC calculation is mentioned below
Sample message, which reads 16 registers from 20h (32 decimal) address, is explained below.
01 03 00 20 00 10 45 CC (each byte is written as 2 hexadecimal characters)
Expected return message is:
BYTE DESCRIPTION
VALUE
0
Controller
Address
Same as query
1
Function Code
3
2
Data Length
Bytes
Register number x 2
3
1.Register Upper
Byte
4
1.Register Lower
Byte
5
2.Register Upper
Byte
6
2.Register Lower
Byte
…
…
…
L+1
Last Register
Upper Byte
L+2
Last Register
Lower Byte
L+3
CRC Lower Byte CRC calculation is mentioned below
L+4
CRC Upper Byte CRC calculation is mentioned below
Failure response message is:
BYTE DESCRIPTION
VALUE
0
Controller
Address
Same as query
1
Function Code
131 (Function code+128)
2
Fail Code
2 (invalid address)
3
CRC Lower Byte CRC calculation is mentioned below
4
CRC Upper Byte CRC calculation is mentioned below
Содержание DKM-409 PRO AT
Страница 20: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 2 3 PHASE 4 WIRE STAR 4 3 3 PHASE 3 WIRE DELTA ...
Страница 21: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 23: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 4 8 1 PHASE 2 WIRE ...
Страница 24: ...DKM 409 Pro AT User Manual Rev_02 Firmware V 2 5 5 CONNECTION DIAGRAM ...