background image

 

                                                          - 95 -                                              

 

 

 

 

 
 

COMMAND 

DESCRIPTION 

RESPONSE 

GET IP  
 

If GPRS connection is active, 
the IP address of the 
connection is sent. 

 

GPRS 1 

GPRS connection enabled. 

 

GPRS 0 

GPRS connection disabled. 

 

RESET 
ALARMS 

Dismisses the alarms on the 
device. Operation mode is not 
changed. 

 

REBOOT 

The unit switches off and on 
again 
 

No response 

RESET MODEM 

The modem of the unit 
switches off and on again 
 

No response 

FORCE STOP 

The unit enters STOP mode. 

 

FORCE RUN 

The unit enters RUN mode. 

 

OUT1 ON 
 

Set remote controlled output 
#1 to active state. 

 

OUT1 OFF 
 

Set remote controlled output 
#1 to passive state. 

 

OUTxx ON 
 

Set remote controlled output 
#xx to active state. (xx denotes 
any number between 1 and 
16) 

 

OUTxx OFF 
 

Set remote controlled output 
#xx to passive state. (xx 
denotes any number between 
1 and 16) 

 

 

User Output xx = 
OFF

 

User Output xx = ON

 

User Output 1 = OFF

 

Unit forced to RUN!

 

User Output 1 = ON

 

Unit forced to STOP!

 

 

SMS messages are only accepted from phone numbers set in 

SMS1-2-3-4 

PHONE NUMBERS 

parameters.  

Responses to SMS messages are sent to all recorded numbers.

 

 

 

SMS messages must be sent exactly as below, without spaces.  

Only 

CAPITAL LETTERS

 must be used.

 

 

Alarms cleared!

 

GPRS disabled!

 

GPRS enabled!

 

IP: 188.41.10.244

 

19. SMS COMMANDS

 

Содержание DK-70

Страница 1: ...gned to conform to highest industrial standards in safety vibration EMC and environmental conditions Firmware updates can be done easily via the USB port The device can be monitored and programmed via...

Страница 2: ...ntact Datakom at the e mail address below technical support datakom com tr If additional information to this manual is required please contact the manufacturer directly at technical support datakom co...

Страница 3: ...PTION 01 26 03 2019 OK First Edition CAUTION Potential risk of injury or death WARNING Potential risk of malfunction or material damage ATTENTION Useful hints for the understanding of device operation...

Страница 4: ...4 Screw type bracket Stock Code J10P01 per unit Self retaining type bracket Stock Code K16P01 per unit Sealing Gasket Stock Code L057P01 SPARE PARTS...

Страница 5: ...efore working on the equipment Do not touch the terminals when the controller is connected to the network Short circuit terminals of unused current transformers Any electrical parameter applied to the...

Страница 6: ...3 13 ETHERNET PORT OPTIONAL 3 14 USB DEVICE PORT 3 15 USB HOST PORT OPTIONAL 3 16 RS 232 PORT OPTIONAL 3 17 GSM MODEM OPTIONAL 3 18 WIFI COMMUNICATION OPTIONAL 4 TOPOLOGIES 4 1 3 PHASE 4 WIRE STAR 4 2...

Страница 7: ...EN MENUS 14 4 MODIFYING PARAMETER VALUE 14 5 EXITING PROGRAMMING MODE 15 PROGRAM PARAMETER LIST 15 1 CONTROLLER CONFIGURATION GROUP 15 2 ELECTRICAL PARAMETERS GROUP 15 3 COMPRESSOR PARAMETERS GROUP 15...

Страница 8: ...21 7 VARIABLE UNLOADED OPERATION TIMER 21 8 PID CONTROL AND ANALOG OUTPUT PWM 21 9 PID CONTROLLD FAN DRIVE 21 10 MOTOR PTC INPUT 21 11 MULTIPLE COMPRESSOR OPERATION 22 MODBUS COMMUNICATION 22 1 PARAM...

Страница 9: ...oltage at measuring terminals beyond the specified range Voltage at digital inputs beyond the specified range Current through measuring terminals beyond the specified range Overload or short circuit a...

Страница 10: ...10 Dimensions 211x162x42mm Panel cutout 176x121mm minimum Weight 500g approx 2 1 DIMENSIONS 2 MOUNTING...

Страница 11: ...s parts of the unit other than the front panel Mount the unit on a flat vertical surface Before mounting remove the mounting brackets and connectors from the unit then pass the through the mounting op...

Страница 12: ...ferent types of brackets are provided Screw type bracket Self retaining type bracket Installation of screw type bracket Installation of self retaining type bracket Do not tighten too much this may bre...

Страница 13: ...0 mm diameter and greater 5 Protected from the amount of dust that would interfere with normal operation 6 Dust tight 2nd Digit Description of Protection Level 0 Not protected 1 Protected against vert...

Страница 14: ...ure range Use adequate cable section at least 0 75mm2 AWG18 Follow national rules for electrical installation Current transformers must have 5A or 1A output For current transformer inputs use at least...

Страница 15: ...nge 0 300 VAC phase neutral 0 520V phase phase Minimum voltage for frequency detection 15 VAC Ph N Supported topologies 3 phase 4 wire star 3 phase 3 wire delta 3 phase 4 wire delta 2 phase 3 wire L1...

Страница 16: ...nge Selecting the CT Rating and Cable Section The load on a CT should be kept to a minimum in order to minimize the phase shift effect of the current transformer Phase shift in a CT will cause erroneo...

Страница 17: ...oth the order of the CTs and their polarities Reactive power measurement is affected by incorrect CT connections in a similar way as active power measurement CORRECT CT CONNECTIONS Let s suppose that...

Страница 18: ...100 0 0 0 100 1 00 Phase L3 100 0 0 0 100 1 00 Total 100 0 0 0 300 0 33 EFFECT OF PHASE SWAPPING The compressor is still loaded with 100 kW in each phase The load power factor PF is 1 PF in phases L2...

Страница 19: ...Wheatstone bridge and instrumentation op amp Measurement Analog resistance measurement Function The measured resistance value is converted to temperature via the preprogrammed PT100 sender curve Analo...

Страница 20: ...med sender curve Nominal input current 4 20mA DC Current measurement range 0 30mA DC Breakdown limit 70mA DC Resolution 12 bit Accuracy 0 5 Noise filtering Yes Number of outputs 0 10V analog output St...

Страница 21: ...og outputs 2 Structure Passive output with two terminals External supply required Function selection From list upper lower limits are programmable Output current range 3 6 22mA DC Input supply voltage...

Страница 22: ...n be programmed from the main controller Any function in the list can be assigned to the desired digital input The number of digital outputs can be increased using the DKG 186 Digital Output FET Expan...

Страница 23: ...cable 200m 115200 baud with 120 ohm balanced cable The RS 485 port features MODBUS RTU protocol Multiple modules can be paralleled on the same RS 485 bus for data transfer to automation or building m...

Страница 24: ...lation 1500 VAC 1 minute Max distance 30m Function Embedded TCP IP Web Server Web Client SMTP e mail SNMP Modbus TCP_IP STANDARD ETHERNET CABLE LED FUNCTIONS GREEN This LED turns on when Ethernet conn...

Страница 25: ...software programming control of the compressors and monitoring of measured parameters are achieved The RainbowPlus software can be downloaded from www datakom com tr The connector on the module is of...

Страница 26: ...s The USB host port is designed for detailed data recording The period of recording is adjustable through program parameter As soon as a USB flash memory is inserted the unit will start data recording...

Страница 27: ...n 5 wire Rx Tx DTR CxD GND Full duplex Baud rate 2400 115200 baud adjustable Data type 8 bit data no parity 1 bit stop Isolation 250VAC 1 minute Max distance 15m Cable type Standard modem cable Connec...

Страница 28: ...t SMTP Modbus TCP IP client SMS e mail Operating temp range 40 C 85 C Data rate max 85 6 kbps download 42 8 kbps upload SIM card type External SIM 3V 1 8V GPRS active Antenna 4 band magnetic with 2m c...

Страница 29: ...Wi Fi protocols 802 11 b g n Frequency range 2 4 GHz 2 5 GHz 2400M 2483 5M Network Protocols IPv4 TCP UDP Security WPA WPA2 Functionality Web Client E mail Modbus TCP_IP 3 18 Wi Fi COMMUNICATION OPTIO...

Страница 30: ...30 Various topologies can be selected from the program parameters 4 2 3 PHASE 4 WIRE DELTA 4 1 3 PHASE 4 WIRE STAR 4 TOPOLOGIES...

Страница 31: ...31 4 4 3 PHASE 3 WIRE DELTA 2 CT L1 L3 4 3 3 PHASE 3 WIRE DELTA 2 CT L1 L2...

Страница 32: ...32 4 6 1 PHASE 2 WIRE 4 5 2 PHASE 3 WIRE DELTA 2 CTs L1 L2...

Страница 33: ...33 5 CONNECTION DIAGRAM...

Страница 34: ...e frequency inverter The output is controlled by a PID loop 7 PRES 12V Pressure sender Supply DC 12V output 70mA max The output supplies the positive to the 4 20mA pressure senders 8 Pressure Sender 3...

Страница 35: ...erm Function Technical data Description 51 Digital Input 1 Digital Inputs 0 150V DC This input is programmable Factory setting User Function 1 52 Digital Input 2 This input is programmable Factory set...

Страница 36: ...AL 0 300V AC Neutral terminal for utility mains 67 MAINS L3 Phase Utility mains phase inputs 0 300V AC Connect the utility mains phases to these terminals High and low limits for mains phase voltages...

Страница 37: ...bit PT100 Input Measurement range 75 240 ohm Accuracy 12 bit Digital inputs Number of inputs 8 Threshold level 6V DC AC 4 20mA Analog outputs Number of outputs 2 Output range 3 6 22mA Accuracy 16 bit...

Страница 38: ...m minimum Weight 500g approx Enclosure High temperature non flammable ROHS compliant ABS PC Mounting Front panel mounted with rear retaining plastic brackets EU Directives Conformity 2014 35 EC Low vo...

Страница 39: ...UNCTIONALITY 7 DESCRIPTION OF CONTROLS LINE MAIN relay status indicator i areti Fault status indicators LCD screen Next screen in the same group LAMP TEST if held pressed Previous group screen Next gr...

Страница 40: ...UTE long press When held pressed for 5 seconds enters PROGRAMMING mode Reset to factory defaults Please refer to RESETTING TO FACTORY DEFAULTS chapter for more details When held pressed for 5 seconds...

Страница 41: ...unters digital output counters demands minimum and maximum values etc Scopemeter Display This group displays waveforms of voltages and currents as an oscilloscope All Ph N and Ph Ph voltages and curre...

Страница 42: ...ture parameters P1 Pressure measured by the 1st pressure sender P2 Pressure measured by the 2nd pressure sender P3 Pressure measured by the 3rd pressure sender P12 Difference of the pressures measured...

Страница 43: ...occurs this LED turns on SERVICE REQUEST If one of the service counters expires this LED turns on PROGRAMMABLE LEDS The controller offers 2 LEDs which can be user defined Any alarm input or relay func...

Страница 44: ...store 100 samples in memory and has 13 bit resolution Sampling rate is 4096Hz This one cycle of a 50Hz signal is represented with 82 points The waveform is displayed on the device screen and on PC scr...

Страница 45: ...em all 31 harmonics will be displayed but on a 60Hz system only 29 harmonics will be shown on screen Graphical Harmonic Table Alphanumeric Harmonics Table Harmonics are represented by 2 different meth...

Страница 46: ...conds resets the min max values Min max values can also be reset from the programming menu relevant parameter ELECTRICAL PARAMETERS Reset Min Max For more robust results min max detection starts 10 se...

Страница 47: ...tarts Alarm bits Digital input and output bits There are various possible event sources Each source can be individually enabled or disabled Program mode entrance event recorded with the password level...

Страница 48: ...nt logs will display the next information in the same event will display the previous information in the same event will display the same information of the previous event will display the same inform...

Страница 49: ...unning hours Number of motor starts Number of fan starts Minutes left until next oil service request 1st digital input pulse counter 2nd digital input pulse counter Engine hours to Service A Engine ho...

Страница 50: ...ses and the motor keeps running for the duration of Safety Timer or Unload Timer whichever is longer If the RUN button is pressed while this timer is counting down the compressor will enter run mode a...

Страница 51: ...aches the Stop Pressure or the pressure switch closes the load relay will release and the motor will run off load for the duration of Unload Timer If the output pressure falls below Start Pressure bef...

Страница 52: ...y Compressor stops immediately 2 WARNINGS These faults are lower priority warnings ALARM LED flashes The alarms feature low high level settings and timers If the fault cause is removed before the prog...

Страница 53: ...y 20 hours The compressor stops Service request warning is given and the service LED turns on The compressor may be run again by pressing the RUN button Between 210 and 300 hours and once every 10 hou...

Страница 54: ...se currents is above the High Current Alarm parameter for the duration of Current Alarm Timer Over Current Alarm occurs HIGH VOLTAGE THD If any of the phase voltages THD Total Harmonic Distortion is a...

Страница 55: ...ifference and the T13 T1 T3 temperature difference exceeds T1 T3 Temperature Difference Alarm parameter or the T23 T2 T3 temperature difference exceeds T2 T3 Temperature Difference Alarm parameter Sen...

Страница 56: ...closed signal from the auxiliary contact is not received within 5 seconds after the main motor contactor closes this alarm occurs MAIN CONTACTOR FAIL TO OPEN If any of the programmable input function...

Страница 57: ...Service A Timer Warning Service B Timer Warning Service C Timer Warning Service D Timer Warning Service E Timer Warning To reset the service counters hold pressed and for 5 seconds Completed will be d...

Страница 58: ...command and the compressor unloads MODBUS TAKE LOAD COMMAND If the Take Load Command Source parameter is set to 2 Modbus Command this warning is issued when the take load command is sent over Modbus...

Страница 59: ...ect device operation To enter the programming mode press together the and buttons for 5 seconds The following password prompt will be displayed upon entering programming mode buttons are used to enter...

Страница 60: ...rogram parameters The selected parameter will be marked with an arrow sign next to it Press the button to view change the parameter value The parameter value is incremented decremented with the button...

Страница 61: ...rformed the controller will exit programming mode automatically after 2 minutes 14 4 MODIFYING PARAMETER VALUE 14 5 EXITING PROGRAMMING MODE Decrement parameter value Increment parameter value Previou...

Страница 62: ...ection 0 5 1 0 no modem no GPS 1 Internal modem no GPS 2 External Datakom modem no GPS 3 External generic modem no GPS 4 No modem RS 232 GPS 5 Internal modem RS 232 GPS GSM SIM Card PIN 0000 9999 0 If...

Страница 63: ...ple operation If the address of any device is set to 32 or lower this compressor is included in the multiple operation network Refer to section 25 11 for further information on multiple operation It i...

Страница 64: ...ssor Fan Stop Together 0 1 1 0 When the compressor turns off Fan OFF Temperature is checked to turn off the fan 1 The fan turns off with the compressor Local Time Zone Hours 12 12 3 This parameter sel...

Страница 65: ...tion of this timer the relevant alarm occurs Voltage Alarm Latching 0 1 0 0 non latching 1 latching Low Frequency Alarm Value Hz 0 400 0 When mains frequency drops below this value an alarm occurs If...

Страница 66: ...f Current Alarm Timer Over Current Alarm occurs If this value is set to 0 the alarm is disabled Current Alarm Timer Sec 0 255 30 If any of the phase currents is outside the limits for the duration of...

Страница 67: ...4 Wire Star 1 1 Phase 2 Wire 2 2 Phase 3 Wire L1 L2 CT 3 3 Phase 4 Wire Delta 4 3 Phase 3 Wire L1 L2 CT 5 3 Phase 3 Wire L1 L3 CT Minimum Displayed Current 0 100 4 This parameter defines the minimum...

Страница 68: ...disengages Heater OFF Temperature Difference C 1 30 5 0 10V Analog Output Configuration 0 25 0 This parameter defines the mode of operation for the 0 10V Analog output 0 Motor Drive 1 Fan Drive 2 Tot...

Страница 69: ...value must be set to the measurement value corresponding to 10V 0 10V Analog Output MAX Value 0 3200 0 0 Inverter Minimum Load Speed rpm 0 9900 1800 The minimum rpm for the motor driven by the inverte...

Страница 70: ...measurement value exceeds this parameter a warning is displayed Low Temperature 1 Alarm Value C 400 400 0 If the 1st temperature measurement value drops below this parameter an alarm occurs Temperatu...

Страница 71: ...s the delay timer for high and low temperature alarms Temperature Sender 2 Offset Value C 20 20 0 This offset parameter is added to the 2nd temperature measurement value Star Duration Sec 2 20 7 This...

Страница 72: ...Wait 1 Hour Before Stopping warning is displayed and the motor is not allowed to stop until the hour is up The motor will not stop even if the pressure is sufficient it continues to run off load Fan...

Страница 73: ...sor stops as explained in section 13 1 when a service timer expires Variable Service Hours 0 1 0 0 Constant service hours coefficient 1 Variable service hours coefficient Explained in detail in sectio...

Страница 74: ...erature Sender 4 Configuration C 0 3 0 0 Disabled 1 Absolute Temperature 2 Temperature Difference 3 Motor PTC MPTC High Temperature alarm occurs when sender measurement value exceeds 2000 Ohms Tempera...

Страница 75: ...PT100 temperature measurement will not be displayed and the relevant alarms will be disabled PT100 High Temperature Alarm Value C 400 400 110 If the PT100 temperature measurement value T5 exceeds thi...

Страница 76: ...Reset Service C Counter 0 1 0 No effect 1 Service C Counter is set equal to the Service C Timer parameter This parameter is not saved to memory it is always read as 0 Reset Service D Counter 0 1 0 No...

Страница 77: ...operation is performed for the compressor The compressor performs load unload cycles until it reaches the Minimum Loading Temperature Pre Heating Offload Timer adjusts the unloaded working duration i...

Страница 78: ...the compressor 0 Temperature Sender 1 T1 1 Temperature Sender 2 T2 2 Temperature Sender 3 T3 3 Temperature Sender 4 T4 4 PT100 Temperature Sender T5 Main Pressure Sender 0 2 0 This parameter selects...

Страница 79: ...ekly operation schedule and start stop automatically the Weekly Operation Schedule Enabled parameter in the Controller Configuration Group must be set to 1 If the Weekly Operation Schedule Enabled par...

Страница 80: ...r s duration is set to 0 it is disabled In order for the compressor to operate according to the Pressure Calendar the Pressure Calendar Enabled parameter in the Controller Configuration Group must be...

Страница 81: ...6 ohm value Sender Curve 6 temp C 32768 32767 20 Step 6 temperature value Sender Curve 7 ohm ohm 0 65535 2080 Step 7 ohm value Sender Curve 7 temp C 32768 32767 30 Step 7 temperature value Sender Cur...

Страница 82: ...e 7 mA mA 0 512 0 10 0 Step 7 mA value Sender Curve 7 pressure bar 0 3000 0 6 0 Step 7 pressure value Sender Curve 8 mA mA 0 512 0 11 0 Step 8 mA value Sender Curve 8 pressure bar 0 3000 0 7 0 Step 8...

Страница 83: ...nder Curve 7 temp C 32768 32767 30 Step 7 temperature value Sender Curve 8 ohm ohm 0 6553 5 115 5 Step 8 ohm value Sender Curve 8 temp C 32768 32767 40 Step 8 temperature value Sender Curve 9 ohm ohm...

Страница 84: ...0 3 0 always 1 When motor is running on or off load 2 When motor running on load 3 If load relay is not closed Latching LAT 0 1 0 non latching The fault is dismissed when the alarm cause is removed 1...

Страница 85: ...lay 18 133 External output module 2 Factory set Not used Relay 19 133 External output module 2 Factory set Not used Relay 20 133 External output module 2 Factory set Not used Relay 21 133 External out...

Страница 86: ...ation 62 Input 14 simulation 63 Input 15 simulation 64 Input 16 simulation 65 User output 1 66 User output 2 67 User output 3 68 User output 4 69 User output 5 70 User output 6 71 User output 7 72 Use...

Страница 87: ...ne site ID Engine serial number is used to identify the compressor on which the controller is mounted In the SMS and e mail messages sent by the controller and also on the webpage the engine serial nu...

Страница 88: ...he correct APN name SMS Service Center No SMS service number may be required by GSM operators However some operators allow SMS sending without entering a service number Refer to your GMS network provi...

Страница 89: ...t Setting documents Membership Address members dyndns org This string is used in Dynamic DNS feature The unit will register itself to the dynamic DNS server under this name For detailed information pl...

Страница 90: ...ility of Internet connection at this interval Rainbow Refresh Rate Sec 0 65535 60 The unit will update the remote monitoring terminal at this rate Rainbow Scada Address 1 Port 80 65535 90 This is the...

Страница 91: ...SNTP Refresh Rate 30 seconds This is the waiting period between two outbound SNTP requests in order to synchronize its internal RTC with the servers SNTP Address 1 Port 123 This is the port number of...

Страница 92: ...ddress are set to 0 0 0 0 then the unit will get the gateway address automatically If you are not an IP professional please leave this address as 0 0 0 0 Subnet Mask 255 255 255 0 Reserved for IP prof...

Страница 93: ...d from GSM system APN User Name The APN access point name username may be required by the GSM operator However some GSM operators may allow access without username The exact information should be obta...

Страница 94: ...uter IPv4 address If the Network IP address and Gateway IP Address are set to 0 0 0 0 then the unit will get the gateway address automatically If you are not an IP professional please leave this addre...

Страница 95: ...ctive state OUT1 OFF Set remote controlled output 1 to passive state OUTxx ON Set remote controlled output xx to active state xx denotes any number between 1 and 16 OUTxx OFF Set remote controlled out...

Страница 96: ...memory or a MICRO SD card is inserted the unit will start data recording and continue until the memory is removed USB FLASH DRIVE 20 1 DATA RECORDING MEDIA The USB Host port and MICRO SD card slot are...

Страница 97: ...90331 meaning March 31 2019 Thus alphabetical listing will produce a sorted list by date of recording The recorded file type is CSV comma separated values This is a text file which can be opened using...

Страница 98: ...der 2 temperature measurement T2 Sender 3 temperature measurement T3 Sender 4 temperature measurement T4 Sender 1 pressure measurement P1 Sender 2 pressure measurement P2 Sender 3 pressure measurement...

Страница 99: ...e L1 L2 and L3 phase measurements will not be displayed on screen The controller offers externally controllable digital output functions To enable this feature the digital outputs must be set to one o...

Страница 100: ...of the main temperature measurement When the variable coefficient calculation method is active Variable Service Hours parameter is set to 1 On load Up to 90 C the multiplier is 1 Between 90 95 C the...

Страница 101: ...he pressure value Pi Restart Pressure at which the motor will restart Pressure Loss Prevention Method 0 None No extra measures taken to prevent pressure loss Pi Start Pressure in all circumstances Pre...

Страница 102: ...eeds Motor PID Start Temperature parameter and starts generating the signal after the Motor PID Start delay expires The motor PID control coefficients can be adjusted from Motor PID P coefficient Moto...

Страница 103: ...he master device and continuously runs according to Stop Pressure and Start Pressure The other devices in the group run and stop according to their engine hours age 3 If any of the devices become youn...

Страница 104: ...lass 10 Supported functions Function 3 read multiple registers Function 6 write single register Function 16 write multiple registers Each register consists of 2bytes 16 bits Larger data structures are...

Страница 105: ...ol the IPv4 input to the device Ethernet Network IP Must be left as 0 0 0 0 if the device is required to receive a dynamic IP The desired static IP address must be entered here in order to give the de...

Страница 106: ...se L2 apparent power 10280 R 32bit x10 Phase L3 apparent power 10282 R 32bit x10 Total apparent power 10284 R 16bit x1000 Phase L1 power factor 10285 R 16bit x1000 Phase L2 power factor 10286 R 16bit...

Страница 107: ...Pressure sender 3 pressure value P3 10459 R 16bit x1 PT100 temperature sender temperature value T5 10460 R 16bit x1 T1 T2 Temperature difference value 10461 R 16bit x1 T1 T3 Temperature difference val...

Страница 108: ...o Service E 10603 R 32bit x1 Number of motor starts counter 10605 R 32bit x1 Number of fan starts counter 10607 R 32bit x1 Time left for oiling minutes counter 10609 R 16bit x1 Controller ID number 10...

Страница 109: ...oltage 10679 R 32bit x10 Phase L2 L3 Maximum voltage 10681 R 32bit x10 Phase L3 L1 Maximum voltage 10683 R 32bit x10 Phase L1 Maximum current 10685 R 32bit x10 Phase L2 Maximum current 10687 R 32bit x...

Страница 110: ...16 status Extension input 8 31 Digital input 32 status Extension input 24 D J TAL OUTPUT R LE DURUM B TLER BIT A IKLAMA BIT A IKLAMA 0 Digital output 4 status 16 Digital output 17 status Extension out...

Страница 111: ...rm 48 Motor Overload Alarm 22 Low Temperature Sender 2 Alarm 49 Main Contactor Fail to Close Alarm 23 Sender 2 Temperature Difference Alarm 50 Main Contactor Fail to Open Alarm 24 Temperature Sender 3...

Страница 112: ...tive alarm 65 User output 2 110 Press Alarm Sender 1 21 Reactive power alarm 66 User output 3 111 Press Alarm Sender 2 22 Capacitive PF alarm 67 User output 4 112 Press Alarm Sender 3 23 Inductive PF...

Страница 113: ...TS BIT DESCRIPTION BIT DESCRIPTION 0 Digital input 1 alarm 4 Digital input 5 alarm 1 Digital input 2 alarm 5 Digital input 6 alarm 2 Digital input 3 alarm 6 Digital input 7 alarm 3 Digital input 4 ala...

Страница 114: ...election If the following decimals are entered into this address the corresponding harmonic channel is selected 0 Phase L1 voltage 1 Phase L2 voltage 2 Phase L3 voltage 6 Phase L1 L2 voltage 7 Phase L...

Страница 115: ...nter 2 8207 W 16bit x1 The value entered into this address is subtracted from Digital input pulse counter 2 8208 W 16bit x1 The value entered into this address is added to Running hours counter 8209 W...

Страница 116: ...orresponding logs can be read 0 Block 0 Event records 1 64 1 Block 1 Event records 65 128 2 Block 2 Event records 129 192 3 Block 3 Event records 193 256 4 Block 4 Event records 257 320 5 Block 5 Even...

Страница 117: ...emperature value 11 R 8bit x1 PT100 sender temperature value 12 R 8bit x1 Reserved 13 14 R 32bit x10 Running hours counter 15 16 R 32bit x10 Loaded running hours counter 17 R 16bit x10 Phase L1 voltag...

Страница 118: ...cimal R W DATA COEFF DESCRIPTION 5120 R 16bit x1 Year 0 4096 5121 R 16bit x1 Month 1 12 5122 R 16bit x1 Day 1 31 5124 R 16bit x1 Hour 0 23 5125 R 16bit x1 Minute 0 59 5126 R 16bit x1 Second 0 59 22 6...

Страница 119: ...I3 Average Minimum Frequency Minimum Active power Minimum Inductive Power Minimum Capacitive Power Max Mains Voltages L1 L2 L3 L12 L23 L31 Maximum Mains Currents I1 I2 I3 Average Maximum Frequency Ma...

Страница 120: ...ired static IP address to give a static IP Ethernet Gateway IP Must be set according to your router Ethernet Subnet Mask Must be set according to your router Please refer to Ethernet Configuration Gui...

Страница 121: ...electrical and electronic equipment WEEE this unit should be stored and disposed separately from usual waste The unit is compliant to DIRECTIVE 2011 65 EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCI...