- 35 -
Term Function
Technical data
Description
19
Relay COM1
Relay COM1 output,
5A/250V-AC
Common terminal for Relay-1-2-3-4.
20
Relay 1 Output
Normally open
outputs 5A/250V-AC
This relay’s function is programmable from
function list. Factory setting is
Compressor MAIN Relay
output.
21
Relay 2 Output
This relay’s function is programmable from
function list. Factory setting is
Compressor DELTA Relay
output.
022
Relay 3 Output
This relay’s function is programmable from
function list. Factory setting is
Compressor STAR Relay
output.
23
Relay 4 Output
This relay’s function is programmable from
function list. Factory setting is
Compressor LOAD Relay
output.
24
Relay 5 Output
These relays’ functions are programmable
from function list. Factory settings are
Input 5-6-7-8 Simulation
outputs
respectively.
25
Relay 6 Output
26
Relay 7 Output
27
Relay 8 Output
28
Relay COM2
Relay COM2 output,
5A/250V-AC
Common terminal for Relay-5-6-7-8.
Term Function
Technical data
Description
51
Digital Input 1
Digital Inputs,
0-150V-DC
This input is programmable. Factory
setting:
User Function 1
52
Digital Input 2
This input is programmable. Factory
setting:
Alarm Mute
53
Digital Input 3
This input is programmable. Factory
setting:
Emergency Stop
54
Digital Input 4
These inputs are programmable. Factory
settings:
Not used
55
Digital Input 5
56
Digital Input 6
57
Digital Input 7
58
Digital Input 8
Term Function
Technical data
Description
59
CU
Current
transformer
inputs, 5A-AC or 1A-
AC
Connect the terminals of current
transformers to these terminals. Do not
connect the same CT to other devices;
this may cause malfunction. Do not use
common terminals. Do not ground. Be
sure to connect each CT to the correct
terminal with the correct polarity.
Otherwise, kW and
cosΦ measurements
will be erroneous. If the measured power
is negative, reverse the polarities of all 3
current transformers. The primary value
of all 3 current transformers must be the
same. Secondary current must be either
1A or 5A. (for example 200/5 A)
60
CURRENT_1-
61
CU
62
CURRENT_2-
63
CU
64
CURRENT_3-
Содержание DK-70
Страница 10: ...10 Dimensions 211x162x42mm Panel cutout 176x121mm minimum Weight 500g approx 2 1 DIMENSIONS 2 MOUNTING...
Страница 31: ...31 4 4 3 PHASE 3 WIRE DELTA 2 CT L1 L3 4 3 3 PHASE 3 WIRE DELTA 2 CT L1 L2...
Страница 32: ...32 4 6 1 PHASE 2 WIRE 4 5 2 PHASE 3 WIRE DELTA 2 CTs L1 L2...
Страница 33: ...33 5 CONNECTION DIAGRAM...