- 23 -
Structure:
RS-485, isolated.
Connection:
3 wire (A-B-GND). Half duplex
Data transfer rate:
2400-115200 baud, adjustable.
Data type:
8-bit data, no parity, 1 bit stop
Isolation:
250VAC, 1 minute
Termination:
External 120-ohm termination resistance required.
Common mode voltage:
-0.5 VDC ... +7VDC, internally clamped by transient suppressors.
Max distance:
1200m @ 9600 baud (with 120-ohm balanced cable)
200m @ 115200 baud (with 120-ohm balanced cable)
The RS-485 port features MODBUS-RTU protocol. Multiple modules can be paralleled on the same RS-
485 bus for data transfer to automation or building management systems.
The RS-485 port provides also a good solution for distant PC connection where RainbowPlus program
will enable programming, control and monitoring.
For more details about programming, control and
monitoring through RS-485 port, please refer to
RainbowPlus user manual.
The Modbus register list is given in chapter 22 of this
document.
3.12. RS-485 PORT (OPTIONAL)