73
MENU K
– ALARMS & LIMITS (Service Level) - Custom Inputs
Alarm Inputs
Custom Alarm Messages
Alarm #1 (DI-13)
SEE TAG INSIDE DOOR
Alarm #2 (DI-14)
SEE TAG INSIDE DOOR
Each of the custom alarm inputs can be given a unique message that will appear
on its alarm screen. Some messages also carry out a function as noted below.
Additional sensors or switches may also be required. The selections are:
SEE TAG INSIDE DOOR (default setting)
REHEAT INHIBITED
– The reheat function is disabled.
HUMIDIFIER INHIBITED
– The humidifier function is disabled.
REHEAT & HUM INHIBITED
– The reheat and humidifier functions are disabled.
UNIT IN STBY
– Not an alarm. Unit status screen will indicate “STANDBY”.
UPS ON-CHK MAIN PWR
STANDBY PUMP ON
CHK HUMIDIFIER CYL
FAN MOTOR OVERLOAD - Inhibits heat and humidifier functions.
AE DAMPER NOT OPEN
– See Airside Economizer Operation
AE DAMPER NOT CLOSED
– See Airside Economizer Operation
POWER A OPERATING
– Message only, does not cause an alarm
POWER B OPERATING
– Message only, does not cause an alarm
POWER A NOT AVAILABLE
POWER B NOT AVAILABLE
COMPRESSOR VFD ALARM
HUM FLT-CHK WTR PR
C1 HIGH PRESSURE
C2 HIGH PRESSURE
C1 LOW PRESSURE
DIRTY FILTER
SMOKE DETECTOR
– Alarm turns the unit off and remains active when unit is off.
NO FLOW-CHECK PUMP
*Note: Some selections require optional equipment.
Содержание dap4 touch
Страница 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Страница 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Страница 55: ...54 MENU J FACTORY SETTINGS factory level continued compressors regardless of the air temperature...
Страница 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Страница 82: ...78...
Страница 133: ...129 Wiring Connections...