– ALARMS & LIMITS (Service Level) continued - Custom Outputs
Alm Output Function 1
#1 #2 #3 #4
CW Sensor
Y
N
N
N
DA Sensor
Y
N
N
N
Fan Ovld
Y
N
N
N
Smoke
Y
N
N
N
Cond Wtr
Y
N
N
N
Firestat
Y
N
N
N
Each of the custom alarm outputs can be assigned to any one or more alarm
conditions or functions. Not all alarms may be configured or applicable to your
specific model. The specific alarm condition will turn on the output alarm when it is
set to Yes
(“Y”). The output will remain on as long as any one of the selected
alarms is active. The default setting for #1 alarm outputs is
“Y”. The default setting
for #2 to #4 alarm outputs is
“N”.
Note: Only Alarm output #1 is available on the Minidap controller. Not all settings
are in the order listed and some are not available in the minidap.
CW Sensor:
Chilled water temperature sensor fault alarm.
DA Sensor:
Discharge air temperature sensor fault alarm.
Fan Ovld:
Fan overload alarm.
Smoke:
Smoke detector alarm.
Cond Wtr:
High condensation water level alarm.
Fire Stat:
Fire status detected alarm