MENU C
– Clock/Scheduler continued
Holiday
Scheduler
Date
Date
Start
Stop
Setting
01/02
12/24
Normal SP
12/24
01/02
Turn Off
--/--
--/--
--------
Note: The Holiday scheduler will override the Special Day and Weekday
schedulers for the dates that the Holiday scheduler is active.
Date Start:
The selection of the date (month/day format) that an action will take
place. You can set up to three actions. Once the date is reached, the action will be
in effect until the Date Stop is reached. The range of adjustment is 01/01 to 12/31.
The default is that no dates are set.
Date Stop:
The selection of the date (month/day format) that an action that began
on the Date Start will end. The range of adjustment is 01/01 to 12/31. The default
is no dates are set.
Setting:
This is the action that should occur at the selected date. This action will
remain until the next start date that is set to have an action. The default value is to
take No Action. There are four possible action settings:
No Action
(--------): The scheduler will continue running the last action
taken either this day or the previous day.
Normal SP:
Use the normal temperature and humidity settings. This action
will also turn the unit on if it was currently off.
Set-Back:
Apply the setback setpoints for temperature and humidity. This
action will also turn the unit on if it was currently off.
Turn Off:
The unit will be turned off until the timed action of Normal SP or
Set-Back is executed. When the unit is off due to the scheduler, the main
status screen will indicate the unit status as OFFbySCH.
Caution: A
“Turn
Off” action must be followed by the “Normal SP” or “Set-Back” action for the
unit to turn back on.
Содержание dap4 touch
Страница 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Страница 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Страница 55: ...54 MENU J FACTORY SETTINGS factory level continued compressors regardless of the air temperature...
Страница 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Страница 82: ...78...
Страница 133: ...129 Wiring Connections...