103
On/Off Compressors Controlling Dewpoint:
In Dewpoint control mode,
compressors are staged according to dewpoint, but the relative humidity level
control shown above is also able to stage compressors on.
Single Compressor
as dewpoint is increasing:
ON at High DP Setpoint
Single Compressor
as dewpoint is decreasing:
OFF at High DP Setpoint minus DP DB
Two Compressor
staging as dewpoint is increasing:
Stage 1 ON at High DP Setpoint minus 0.2°F
Stage 2 ON at High DP Setpoint
Two Compressor
staging as dewpoint is decreasing:
Stage 2 OFF at High DP Setpoint minus DP DB
Stage 1 OFF at High DP Setpoint minus DP DB minus 0.2°F
Four Compressor
staging as dewpoint is increasing:
Stage 1 ON at High DP Setpoint minus 0.6°F
Stage 2 ON at High DP Setpoint minus 0.4°F
Stage 3 ON at High DP Setpoint minus 0.2°F
Stage 4 ON at High DP Setpoint
Four Compressor
staging as dewpoint is decreasing:
Stage 4 OFF at High DP Setpoint minus DP DB
Stage 3 OFF at High DP Setpoint minus DP DB minus 0.2°F
Stage 2 OFF at High DP Setpoint minus DP DB minus 0.4°F
Stage 1 OFF at High DP Setpoint minus DP DB minus 0.6°F
Note:
If Humidity Anticipation is enabled, the setpoint in the above examples could
be offset as much as 10% depending on how far temperature is from the
temperature setpoint.
Содержание dap4 touch
Страница 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Страница 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Страница 55: ...54 MENU J FACTORY SETTINGS factory level continued compressors regardless of the air temperature...
Страница 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Страница 82: ...78...
Страница 133: ...129 Wiring Connections...