MENU H - CALIBRATE SENSORS (
Service Level)
Analog Input
Humidity Sensor
Input U01
Offset:
00.0
Value:
45.8
This menu is used to allow analog sensors to be calibrated by a service technician
using a calibrated instrument. Each screen in this menu identifies the function of
the sensor and the terminal that the sensor is connected to.
Offset:
The amount that the sensor needs to be corrected by so that the meter
value will match the value shown on the screen. Range of adjustment is -99.0 to
99.0 with a default value of 0.0.
Value:
The current reading of the sensor including the offset setting.