77
MENU K
– ALARMS & LIMITS (Service Level) continued - Custom Outputs
Alm Output Function 6
#1 #2 #3 #4
Unit Stdby
Y
N
N
N
UPS is On
Y
N
N
N
Stdby Pump
Y
N
N
N
Hum Cyl
Y
N
N
N
C1 Lockout
Y
N
N
N
C2 Lockout
Y
N
N
N
Unit Stdby:
Unit in standby by custom alarm input.
UPS is On:
Custom alarm input set for
“UPS ON” mode.
Stdby Pump:
Custom alarm input set for
“STANDBY PUMP ON” mode.
Hum Cyl:
Custom alarm input set for
“CHK HUMIDIFIER CYL” mode.
C1 Lockout:
Compressor circuit 1 locked out alarm.
C2 Lockout:
Compressor circuit 2 locked out alarm.
Alm Output Function 7
#1 #2 #3 #4
FreezeStat
Y
N
N
N
Rack Hi T
Y
N
N
N
Rack Low T
Y
N
N
N
Rack Sns F
Y
N
N
N
EVD Fault
Y
N
N
N
Lost Phase
Y
N
N
N
FreezeStat:
Freeze Status alarm.
Rack Hi T:
One or more rack sensors in high temperature alarm.
Rack Low T:
One or more rack sensors in low temperature alarm.
Rack Sns F:
Failure of one or more rack sensors alarm.
EVD Fault:
EVD has a critical alar condition.
Lost Phase:
Lost phase detected by optional power meter.
Содержание dap4 touch
Страница 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Страница 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Страница 55: ...54 MENU J FACTORY SETTINGS factory level continued compressors regardless of the air temperature...
Страница 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Страница 82: ...78...
Страница 133: ...129 Wiring Connections...