– ALARMS & LIMITS (Service Level) continued
Flow Alarms
No Water Flow Action:
Alarm Only
Wtr Flow Alm Dly:
60s
Air Flow Alm Dly:
60s
No Water Flow Action:
The water flow alarm cannot be disabled and is checked
only when there is a need for DX cooling or if the CW valve has opened at least
60%. This setting determines what should happen when the alarm occurs. (Note: a
flow sensor required).
Alarm Only:
(Default) The alarm will not cause any change in operation.
Turn Compressors Off:
The compressors will be shut down and kept off
for 5 minutes after the water flow alarm is no longer active. A countdown
showing the time remaining until the compressors will be allowed to run is
shown on the no water flow alarm screen.
Lockout CW:
The CW cooling will be locked out for ES Lockout Time
before CW cooling will be allowed to function again. A countdown showing
the time remaining until CW will be allowed to run is shown on the no water
flow alarm screen.
Lockout Both CW & DX:
Operates as the CW lockout does but
compressors will also be lockout along with the CW being locked out.
Wtr Flow Alm Dly:
This is the amount of time that the water flow alarm is
delayed from occurring. The selection is from 5 to 180 seconds with a
default of 5 seconds.
No Air Flow:
The air flow alarm cannot be disabled and is checked when the fan
is on. The alarm is delayed for about a minute when the system is initially turned
on.
Air Flow Alm Dly:
This is the amount of time that the air flow alarm is
delayed from occurring. The selection is from 5 to 180 seconds with a
default of 5 seconds.
Содержание dap4 touch
Страница 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Страница 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Страница 55: ...54 MENU J FACTORY SETTINGS factory level continued compressors regardless of the air temperature...
Страница 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Страница 82: ...78...
Страница 133: ...129 Wiring Connections...