24
MENU C
– Clock/Scheduler continued
Set-Back Settings
Cooling Setpoint:
77.0• Heating
Setpoint: 67.0•
Humidify Offset:
55%
Dehumidify Offset: 45%
Note on gPOD models:
In addition to the clock/time schedular, Night Time
setpoints are also used when an optional light sensor detects an absence of light
(input is turned on).
Cooling Setpoint:
Temperature set point for cooling, used when the scheduler is
in set-back mode. The range of adjustment depends the temperature being
controlled:
Return air: range is 65 to 85°F with a default value of 77°F.
Discharge air: range is 45 to 85°F with a default value of 77°F.
(If model is IRDX or CW only (no DX), maximum range increases to 105°F)
Heating Setpoint:
Temperature set point for heating, used when the scheduler is
in set-back mode. The range of adjustment depends the temperature being
controlled:
Return air: range is 65 to 85°F with a default value of 67°F.
Discharge air: range is 45 to 85°F with a default value of 67°F.
(If model is IRDX or CW only (no DX), maximum range increases to 105°F)
Humidify Setpoint:
The humidifier setpoint, used when the scheduler is in set-
back mode. The range of adjustment is 25 to 70% with a default value of 45%.
Dehumidify Setpoint:
The dehumidification setpoint, used when the scheduler is
in set-back mode. The range of adjustment is 25 to 70% with a default value of
55%.
Содержание dap4 touch
Страница 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Страница 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Страница 55: ...54 MENU J FACTORY SETTINGS factory level continued compressors regardless of the air temperature...
Страница 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Страница 82: ...78...
Страница 133: ...129 Wiring Connections...