71
MENU K
– ALARMS & LIMITS (Service Level) continued
Pump-Down Alarm
Failed PD Alarm:
Yes
Note: Pump-Down
feature will still
operate.
The Pump-Down Alarm screen will only appear if the feature is enabled in the
Factory menu.
Failed PD alarm:
When set to
“Yes” (default) the pump-down alarm is enabled. If
set to
“No”, the pump-down cycle will still operate, but without an alarm. The PD
alarm results from a PD cycle taking too long or if there are more than three PD
cycles required.
Phase Loss
Alarm
Action: No Alarm
This Phase Loss Alarm screen is only shown when the optional power meter is
installed and configured in the factory menu.
Action:
The action to a phase loss alarm setting has three choices:
No Alarm:
(Default setting). The phase alarm is disabled.
Alarm Only:
The phase alarm is enabled but has no further action.
Alm & Turn Off:
The phase alarm is enabled and will cause the unit to turn
off in the event of the alarm.