1.6 Ratings Tables
DC Voltage Levels
380-480 V &
380-500 V
units
525-690 V
units
Inrush Circuit Enabled
370
550
Inrush Circuit Disabled
395
570
Inverter Undervoltage Disable
373
553
Undervoltage Warning
410
585
Inverter Undervoltage Re-Enable
(warning reset)
413
602
Overvoltage Warning (w/o Brake)
817
1084
Dynamic Brake Turn-on
810
1099
Inverter Overvoltage Re-Enable
(warning reset)
821
1099
Overvoltage Warning (with Brake)
828
1109
Overvoltage Trip
855
1130