Speed high
In
4-53 Warning Speed High
, a value is set. The speed of the
motor is above this value.
Speed low
In
4-52 Warning Speed Low
, a value is set. The speed of the
motor is below this value.
Standby
[Auto on] The FC starts the motor using a start signal in a
digital input (if the parameter is programmed accordingly)
or via serial communication.
Start delay
In
1-71 Start Delay
, the delay of the starting time was set. A
Start command was activated and the delay time is still
running. The motor will start after the delay time has
expired.
Start fwd/rev
Enable start forward
and
Enable start reverse
were selected
as functions for two different digital inputs (parameter
group 5-1*). To start the motor, a direction dependent
start signal has to be given and the corresponding
terminal has to be active.
Start inhibit
PROFIDrive profile
was selected in
8-10 Control Word Profile
.
The start inhibition is active. The FC needs the first part
(e.g. 0x047E) of the two-part start command via serial
communication to allow starting. See also operation status
control ready.
Stop
[Off] was pressed on the LCP or Stop inverse was selected
as a function for a digital input (Group 5-1*). The
corresponding terminal is not active.
Trip
An alarm occurred. It is possible, provided the cause of the
alarm is cleared, to reset the alarm via a
Reset
signal
([Reset] key on the LCP, a control terminal or serial
communication).
Trip lock
A serious alarm occurred. It is possible, provided the cause
of the alarm was cleared, to reset the alarm after the
mains have been switched off and on again. This can be
done via a
reset
signal ([Reset] on the LCP, a control
terminal or serial communication).
Unit/Drive not ready
PROFIDrive profile
was selected in
8-10 Control Word Profile
.
A control word is sent to the FC via serial communication
with Off 1, Off 2 and Off 3 active. Start inhibit is active. To
enable start, see operation status Start inhibit.
2.4 Service Functions
Service information for the frequency converter can be
shown on display lines 3 and 4. Included in the data are
counters that tabulate operating hours, power ups and
trips; fault logs that store frequency converter status values
present at the 20 most recent events that stopped the
frequency converter and frequency converter nameplate
data. The service information is accessed by displaying
items in the frequency converter's 15-** parameter group.
Parameter settings are displayed by pressing the [Main
Menu] key on the LCP.
130BP045.10
Status
Quick
Menu
Main
Menu
Alarm
Log
Use the arrow keys [
▲
], [
▼
], [
►
] and [
◄
] on the LCP to scroll
through parameters.
Auto
on
Reset
Hand
on
Off
Status
Quick
Menu
Main
Menu
Alarm
Log
Back
Canc
el
In
fo
OK
On
Alarm
Warn.
130BA027.10
See the FC Series Programming Guide for detailed
information on accessing and displaying parameters and
Operator Interface and Cont...
High Power Service Manual for Modular F Frame Drives
42
MG90K202 - VLT
®
is a registered Danfoss trademark
2