Mains Supply 6 x 380 - 500 VAC, 12-Pulse
FC 302
P450
P500
P560
P630
P710
P800
High/ Normal Load *
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output at 400 V
[kW]
450
500
500
560
560
630
630
710
710
800
800
1000
Typical Shaft output at 460 V
[HP]
600
650
650
750
750
900
900
1000
1000
1200
1200
1350
Typical Shaft output at 500 V
[kW]
530
560
560
630
630
710
710
800
800
1000
1000
1100
EnclosureIP21, 54 without/
with options cabinet
F10/F11
F10/F11
F10/F11
F10/F11
F12/F13
F12/F13
Output current
Continuous
(at 400 V) [A]
800
880
880
990
990
1120
1120
1260
1260
1460
1460
1720
Intermittent (60 sec overload)
(at 400 V) [A]
1200
968
1320
1089
1485
1232
1680
1386
1890
1606
2190
1892
Continuous
(at 460/ 500 V) [A]
730
780
780
890
890
1050
1050
1160
1160
1380
1380
1530
Intermittent (60 sec overload)
(at 460/ 500 V) [A]
1095
858
1170
979
1335
1155
1575
1276
1740
1518
2070
1683
Continuous KVA
(at 400 V) [KVA]
554
610
610
686
686
776
776
873
873
1012
1012
1192
Continuous KVA
(at 460 V) [KVA]
582
621
621
709
709
837
837
924
924
1100
1100
1219
Continuous KVA
(at 500 V) [KVA]
632
675
675
771
771
909
909
1005
1005
1195
1195
1325
Max. input current
Continuous
(at 400 V) [A]
779
857
857
964
964
1090
1090
1227
1227
1422
1422
1675
Continuous (at 460/ 500 V) [A]
711
759
759
867
867
1022
1022
1129
1129
1344
1344
1490
Max. cable size,motor [mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable size,mains [mm
2
(AWG
2)
)]
6x120
(6x250 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
4x185
(4x350 mcm)
6x185
(6x350 mcm)
Max. external mains fuses [A]
1
900
1500
Estimated power loss
at 400 V [W]
4)
9492
10647
10631
12338
11263
13201
13172
15436
14967
18084
16392
20358
Estimated power loss
at 460 V [W]
8730
9414
9398
11006
10063
12353
12332
14041
13819
17137
15577
17752
F9/F11/F13 max. added losses
A1 RFI, CB or Disconnect, &
contactor F9/F11/F13
893
963
951
1054
978
1093
1092
1230
2067
2280
2236
2541
Max. panel options losses
400
Weight,
enclosure IP21, IP 54 [kg]
1004/ 1299
1004/ 1299
1004/ 1299
1004/ 1299
1246/ 1541
1246/ 1541
Weight Rectifier Module [kg]
102
102
102
102
136
136
Weight Inverter Module [kg]
102
102
102
136
102
102
Efficiency
4)
0.98
Output frequency
0-600 Hz
Heatsink overtemp. trip
95 °C
Power card ambient trip
75 °C
* High overload = 160% torque during 60 sec., Normal overload = 110 % torque during 60 sec.