![Danfoss VLT HVAC Drive FC100 Скачать руководство пользователя страница 118](http://html1.mh-extra.com/html/danfoss/vlt-hvac-drive-fc100/vlt-hvac-drive-fc100_service-manual_3693478118.webp)
8.2.7 Gate Drive Card
1.
Disconnect cables from gate drive card connectors MK100, MK102, MK103, MK104, MK106, and, if unit has a brake
option MK105.
2.
Remove gate drive card by removing 6 mounting screws (T25) from standoffs.
Reinstall in reverse order of this procedure. Tighten
mounting screws to 2.3 Nm (20 in-lbs).
1
2
3
4
5
6
130BX256.10
1
MK104 (W)
4
MK100
2
MK103 (V)
5
MK105 (brake option)
3
MK102 (U)
6
MK106
Disassembly/Assembly - Inve...
High Power Service Manual for Modular F Frame Drives
MG90K202 - VLT
®
is a registered Danfoss trademark
117
8