![Danfoss VLT HVAC Drive FC100 Скачать руководство пользователя страница 125](http://html1.mh-extra.com/html/danfoss/vlt-hvac-drive-fc100/vlt-hvac-drive-fc100_service-manual_3693478125.webp)
9.2.10 Diode Module
1.
Remove power card mounting plate in
accordance with instructions.
2.
Remove soft charge mounting plate in
accordance with instructions.
3.
Remove two mounting nuts (17 mm) from diode
module, one on AC input side and one on (-) DC
side of module.
4.
Remove diode module by removing four
retaining screws (T30) and washers from corners
of module.
Reassembly
1.
Replace diode module in accordance with
instructions included with replacement module.
2.
Reassemble in reverse order of this procedure.
1
2
3
1
17 mm retaining nut (step 3)
2
T30 screws (step 4)
3
Diode module
Disassembly/Assembly - Rect...
High Power Service Manual for Modular F Frame Drives
124
MG90K202 - VLT
®
is a registered Danfoss trademark
9
9