1.5 Frame Size Definitions
1.5.1 F-Frame Size Definitions
380-480 VAC
Power
Model FC 102FC 102,
FC-202 VLT AQUA
Drive
kW
@
400 VAC
HP
@
460 VAC
Frame Size
P500
500
650
F1 / F3
P560
560
750
F1 / F3
P630
630
900
F1 / F3
P710
710
1000
F1 / F3
P800
800
1200
F2 / F4
P1M0
1000
1350
F2 / F4
Table 1.1 FC 102FC 102, FC 202 380-480 VAC
380-500 VAC
Power
Model FC 302
High / Normal Overload
kW
@
400
VAC
HP
@
460
VAC
kW
@
500
VAC
Frame Size
P450
450 / 500
600/ 650
530 / 560
F1 / F3
P500
500 / 560
650 / 750
560 / 630
F1 / F3
P560
560 / 630
750 / 900
630 / 710
F1 / F3
P630
630 / 710
900 / 1000
710 / 800
F1 / F3
P710
710 / 800
1000 / 1200
800 / 1000
F2 / F4
P800
800 / 1000
1200 / 1350 1000 / 1100
F2 / F4
Table 1.2 FC 302 380-500 VAC
525-690 VAC
Power
Model FC 102FC
102 and FC-202
VLT AQUA Drive
kW
@
550
VAC
HP
@
575
VAC
kW
@
690
VAC
Frame Size
P710
560
750
710
F1 / F3
P800
670
950
800
F1 / F3
P900
750
1050
900
F1 / F3
P1M0
950
1150
1000
F2 / F4
P1M2
1000
1350
1200
F2 / F4
P1M4
1100
1550
1400
F2 / F4
Table 1.3 FC 102FC 102 and FC 202 525-690 VAC
525-690 VAC
Power
Model FC 302
High / Normal Overload
kW
@
550
VAC
HP
@
575
VAC
kW
@
690
VAC
Frame Size
P630
500 / 560
650 / 750
630 / 710
F1 / F3
P710
560 / 670
750 / 950
710 / 800
F1 / F3
P800
670 / 750
950 / 1050
800 / 900
F1 / F3
P900
750 / 850
1050 / 1150
900 / 1000
F2 / F4
P1M0
850 / 1000
1150 / 1350 1000 / 1200
F2 / F4
P1M2
1000 / 1100 1350 / 1550 1200 / 1400
F2 / F4
Table 1.4 FC 302 525-690 VAC
1.5.2 12-Pulse Frame Size Definitions
380-480 VAC
Power
Model 12-pulseFC
102FC 102, FC-202
VLT AQUA Drive
kW
@
400 VAC
HP
@
460 VAC
Frame Size
P315
315
450
F8 / F9
P355
355
500
F8 / F9
P400
400
550
F8 / F9
P450
450
600
F8 / F9
P500
500
650
F10 / F11
P560
560
750
F10 / F11
P630
630
900
F10 / F11
P710
710
1000
F10 / F11
P800
800
1200
F12 / F13
P1M0
1000
1350
F12 / F13
Table 1.5 12-Pulse FC 102FC 102, FC 202 380-480 VAC
380-500 VAC
Power
Model FC 302
High / Normal Overload
kW
@
400
VAC
HP
@
460
VAC
kW
@
500
VAC
Frame Size
P250
250 / 315
350 / 450
315 / 355
F8 / F9
P315
315 / 355
450 / 500
355 / 400
F8 / F9
P355
355 / 400
500 / 550
400 / 450
F8 / F9
P400
400 / 450
550 / 600
500 / 530
F8 / F9
P450
450 / 500
600/ 650
530 / 560
F10 / F11
P500
500 / 560
650 / 750
560 / 630
F10 / F11
P560
560 / 630
750 / 900
630 / 710
F10 / F11
P630
630 / 710
900 / 1000
710 / 800
F10 / F11
P710
710 / 800
1000 / 1200
800 / 1000
F12 / F13
P800
800 / 1000
1200 / 1350 1000 / 1100
F12 / F13
Table 1.6 12-Pulse FC 302 380-500 VAC
525-690 VAC
Power
Model FC 102FC
102 and FC-202
VLT AQUA Drive
kW
@
550
VAC
HP
@
575
VAC
kW
@
690
VAC
Frame Size
P450
450
450
-
F8 / F9
P500
500
500
-
F8 / F9
P560
560
600
-
F8 / F9
P630
600
650
-
F8 / F9
P710
560
750
710
F10 / F11
P800
670
950
800
F10 / F11
P900
750
1050
900
F10 / F11
P1M0
950
1150
1000
F12 / F13
P1M2
1000
1350
1200
F12 / F13
P1M4
1100
1550
1400
F12 / F13
Table 1.7 12-Pulse FC 102FC 102 and FC 202 525-690 VAC
525-690 VAC
Power
Model FC 302
High / Normal Overload
kW
@
550
VAC
HP
@
575
VAC
kW
@
690
VAC
Frame Size
P355
300 / 355
400 / 450
355 / 450
F8 / F9
P400
315 / 400
450 / 500
400 / 500
F8 / F9
P500
400 / 450
500 / 600
500 / 560
F8 / F9
P560
450 / 500
600 / 650
560 / 630
F8 / F9
P630
500 / 560
650 / 750
630 / 710
F10 / F11
P710
560 / 670
750 / 950
710 / 800
F10 / F11
P800
670 / 750
950 / 1050
800 / 900
F10 / F11
P900
750 / 850
1050 / 1150
900 / 1000
F12 / F13
P1M0
850 / 1000
1150 / 1350 1000 / 1200
F12 / F13
P1M2
1000 / 1100 1350 / 1550 1200 / 1400
F12 / F13
Table 1.8 12-Pulse FC 302 525-690 VAC
Introduction
High Power Service Manual for Modular F Frame Drives
MG90K202 - VLT
®
is a registered Danfoss trademark
7
1
1