![Danfoss VLT HVAC Drive FC100 Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/danfoss/vlt-hvac-drive-fc100/vlt-hvac-drive-fc100_service-manual_3693478017.webp)
1.7.2 FC 300
1.7.2.1 Mains Supply 3 x 380 - 480/500 VAC
Mains Supply 6 x 380 - 500V AC, 12-Pulse
FC 302
P250
P315
P355
P400
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output at 400 V [kW]
250
315
315
355
355
400
400
450
Typical Shaft output at 460 V [HP]
350
450
450
500
500
600
550
600
Typical Shaft output at 500V [kW]
315
355
355
400
400
500
500
530
Enclosure IP21
F8/F9
F8/F9
F8/F9
F8/F9
Enclosure IP54
F8/F9
F8/F9
F8/F9
F8/F9
Output current
Continuous
(at 400V) [A]
480
600
600
658
658
745
695
800
Intermittent (60 sec overload)
(at 400 V) [A]
720
660
900
724
987
820
1043
880
Continuous
(at 460/ 500V) [A]
443
540
540
590
590
678
678
730
Intermittent (60 sec overload)
(at 460/ 500V) [A]
665
594
810
649
885
746
1017
803
Continuous KVA
(at 40 V) [KVA]
333
416
416
456
456
516
482
554
Continuous KVA
(at 460 V) [KVA]
353
430
430
470
470
540
540
582
Continuous KVA
(at 500V) [KVA]
384
468
468
511
511
587
587
632
Max. input current
Continuous
(at 400 V ) [A]
472
590
590
647
647
733
684
787
Continuous
(at 460/ 500V) [A]
436
531
531
580
580
667
667
718
Max. cable size, mains [mm
2
(AWG
2)
)]
4x90 (3/0)
4x90 (3/0)
4x240 (500 mcm)
4x240 (500 mcm)
Max. cable size, motor [mm
2
(AWG
2)
)]
4x240
(4x500 mcm)
4x240
(4x500 mcm)
4x240
(4x500 mcm)
4x240
(4x500 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external mains fuses [A]
1
700
Estimated power loss
at 400 V [W]
4)
5164
6790
6960
7701
7691
8879
8178
9670
Estimated power loss
at 460 V [W]
4822
6082
6345
6953
6944
8089
8085
8803
Weight,enclosure IP21, IP 54 [kg]
440/656
Efficiency
4)
0.98
Output frequency
0 - 60 Hz
Heatsink overtemp. trip
95° C
Power card ambient trip
75° C
* High overload = 160 % torque during 60 sec., Normal overload = 110 % torque during 60 sec.