Mains Supply 3 x 525- 690V AC
P710
P800
P900
Typical Shaft output at 550 V [kW]
560
670
750
Typical Shaft output at 575 V [HP]
750
950
1050
Typical Shaft output at 690 V [kW]
710
800
900
Enclosure IP21, 54 without/ with options
cabinet
F10/F11
F10/F11
F10/F11
Output current
Continuous
(at 550 V) [A]
763
889
988
Intermittent (60 sec overload)
(at 550 V) [A]
839
978
1087
Continuous
(at 575/ 690 V) [A]
730
850
945
Intermittent (60 sec overload)
(at 575/ 690 V) [A]
803
935
1040
Continuous KVA
(at 550 V) [KVA]
727
847
941
Continuous KVA
(at 690 V) [KVA]
872
1016
1129
Max. input current
Continuous
(at 550 V ) [A]
743
866
962
Continuous
(at 575 V) [A]
711
828
920
Continuous
(at 690 V) [A]
711
828
920
Max. cable size, motor [mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
Max. cable size,mains [mm
2
(AWG
2)
)]
6x120
(6x250 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
4x185
(4x350 mcm)
Max. external mains fuses [A]
1
900
Estimated power loss
at 600 V [W]
4)
10771
12272
13835
Estimated power loss
at 690V [W]
4)
11315
12903
14533
F3/F4 Max added losses CB or Disconnect &
Contactor
427
532
615
Max panel options losses
400
Weight,
enclosure IP21, IP 54 [kg]
1004/ 1299
1004/ 1299
1004/ 1299
Weight, Rectifier Module [kg]
102
102
102
Weight, Inverter Module [kg]
102
102
136
Efficiency
4)
0.98
Output frequency
0-500 Hz
Heatsink overtemp. trip
85 °C
Power card ambient trip
68 °C
* High overload = 160% torque during 60 sec., Normal overload = 110% torque during 60 sec.