![Danfoss VLT HVAC Drive FC100 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/danfoss/vlt-hvac-drive-fc100/vlt-hvac-drive-fc100_service-manual_3693478012.webp)
1.7 12-Pulse Ratings Tables
1.7.1 FC 100 and FC 200
1.7.1.1 Mains Supply 3 x 380 - 480/500 VAC
Mains Supply 6 x 380 - 500V AC
P315
P355
P400
P450
Typical Shaft output at 400 V [kW]
315
355
400
450
Typical Shaft output at 460 V [HP]
450
500
600
600
Typical Shaft output at 500 V [kW]
355
400
500
530
Enclosure IP21
F8/F9
F8/F9
F8/F9
F8/F9
Enclosure IP54
F8/F9
F8/F9
F8/F9
F8/F9
Output current
Continuous
(at 400 V) [A]
600
648
745
800
Intermittent (60 sec overload)
(at 400 V) [A]
660
724
820
880
Continuous
(at 460/ 500 V) [A]
540
590
678
730
Intermittent (60 sec overload)
(at 460/ 500 V) [A]
594
649
746
803
Continuous KVA
(at 400 V) [KVA]
416
456
516
554
Continuous KVA
(at 460 V) [KVA]
430
470
540
582
Continuous KVA
(at 500 V) [KVA]
468
511
587
632
Max. input current
Continuous
(at 400 V ) [A]
590
647
733
787
Continuous
(at 460/ 500 V) [A]
531
580
667
718
Max. cable size, mains [mm
2
(AWG
2)
)]
4x90 (3/0)
4x90 (3/0)
4x240 (500 mcm)
4x240 (500 mcm)
Max. cable size, motor [mm
2
(AWG
2)
)]
4x240
(4x500 mcm)
4x240
(4x500 mcm)
4x240
(4x500 mcm)
4x240
(4x500 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external mains fuses [A]
1
700
Estimated power loss
at 400 V [W]
4)
6790
7701
8879
9670
Estimated power loss
at 460 V [W]
6082
6953
8089
8803
Weight,enclosure IP21, IP 54 [kg]
440/656
Efficiency
4)
0.98
Output frequency
0 - 600Hz
Heatsink overtemp. trip
95 °C
Power card ambient trip
68 °C
* High overload = 160% torque during 60 sec, Normal overload = 110% torque during 60 sec.
Introduction
High Power Service Manual for Modular F Frame Drives
MG90K202 - VLT
®
is a registered Danfoss trademark
11
1
1