5.3.5 Proper EMC Installation
Shown in the illustration below is a correct installation
with EMC considerations in mind. Although most instal-
lations will not follow all the recommended practices the
closer an installation resembles this example the better
immunity the network will have against EMI. Should EMI
problems arise in an installation, refer to this example.
Attempt to replicate this installation recommendation as
closely as possible to alleviate such problems.
130BA048.13
L1
L2
L3
PE
Min. 16 mm
2
Equalizing cable
Control cables
All cable entries in
one side of panel
Earthing rail
Cable insula-
tion stripped
Output con-
tactor etc.
Min. 200mm
between con-
trol cables,
motor cable and
Motor cable
Motor, 3 phases and
PLC etc.
Panel
Mains-supply
mains cable
PLC
Protective earth
Reinforced protective earth
Illustration 5.6 Proper EMC Installation