Conventions
Numbered lists show procedures.
Bullet lists show additional information.
Italicized text shows cross-references, links, and parameters.
All measurements are presented as metric units (imperial units).
8.2 International/North American Default Parameter Settings
Setting
parameter 0-03 Regional Settings
to
[0] International
or
[1] North America
changes the default settings for some
parameters.
lists those parameters that are affected. Changes made to the default settings are stored. They are
available for viewing in the quick menu, along with any programming entered into the parameters.
Parameter
International Default Parameter Value
North American Default Parameter Value
Parameter 0-03 Regional Settings
International
North America
Parameter 0-71 Date Format
DD-MM-YYYY
MM/DD/YYYY
Parameter 0-72 Time Format
24 h
12 h
Parameter 1-20 Motor Power [kW]
See Note
1)
See Note
1)
Parameter 1-21 Motor Power [HP]
See Note
2)
See Note
2)
Parameter 1-22 Motor Voltage
230 V/400 V/575 V
208 V/460 V/575 V
Parameter 1-23 Motor Frequency
50 Hz
60 Hz
Parameter 3-03 Maximum Reference
50 Hz
60 Hz
Parameter 3-04 Reference Function
Sum
External/Preset
Parameter 4-13 Motor Speed High Limit [RPM]
3)
1500 RPM
1800 RPM
Parameter 4-14 Motor Speed High Limit [Hz]
4)
50 Hz
60 Hz
Parameter 4-19 Max Output Frequency
100 Hz
120 Hz
Parameter 4-53 Warning Speed High
1500 RPM
1800 RPM
Parameter 5-12 Terminal 27 Digital Input
Coast inverse
External interlock
Parameter 5-40 Function Relay
Alarm
No alarm
Parameter 6-15 Terminal 53 High Ref./Feedb.
Value
50
60
Parameter 6-50 Terminal 42 Output
Speed 0–HighLim
Speed 4–20 mA
Parameter 14-20 Reset Mode
Manual reset
Infinite auto reset
Parameter 22-85 Speed at Design Point [RPM]
3)
1500 RPM
1800 RPM
Parameter 22-86 Speed at Design Point [Hz]
50 Hz
60 Hz
Parameter 24-04 Fire Mode Max Reference
50 Hz
60 Hz
Table 8.2 International/North American Default Parameter Settings
1) Parameter 1-20 Motor Power [kW] is visible only when parameter 0-03 Regional Settings is set to [0] International.
2) Parameter 1-21 Motor Power [HP]is visible only when parameter 0-03 Regional Settings is set to [1] North America.
3) This parameter is visible only when parameter 0-02 Motor Speed Unit is set to [0] RPM.
4) This parameter is visible only when parameter 0-02 Motor Speed Unit is set to [1] Hz.
8.3 Parameter Menu Structure
Certain parameters are specific to the drive system. For a list of these parameters and all other system parameters, including
descriptions, refer to the
programming guide
applicable to the series of drive modules used in creating the drive system.
Appendix
VLT
®
Parallel Drive Modules
72