5.3.4 Potentiometer Reference
Voltage reference via a potentiometer
Reference source 1 =
[1] Analog input 53
(default).
Terminal 53, Low voltage = 0 V.
Terminal 53, High voltage = 10 V.
Terminal 53, Low ref./feedback = 0 RPM.
Terminal 53, High ref./feedback = 1500 RPM.
Switch S201 = OFF (U).
130BA154.11
55
50
39 42
53 54
Speed RPM
P 6-15
1 k
Ω
+10V/30mA
Ref. voltage
P 6-11 10V
Illustration 5.8 Potentiometer Voltage Reference
Application Set-up Examples
VLT
®
Parallel Drive Modules
30
Danfoss A/S © 08/2017 All rights reserved.
MG37L202