Power range
N630
N710
N800
N900
N1M0
Drive modules
4
4
4
4
4
Rectifier configuration
6-pulse/12-pulse
High/normal load
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at 525–550 V [kW]
500
560
560
670
670
750
750
850
850
1000
Typical shaft output at 575 V [hp]
650
750
750
950
950
1050
1050
1150
1150
1350
Typical shaft output at 690 V [kW]
630
710
710
800
800
900
900
1000
1000
1200
Protection rating
IP00
Efficiency
0.98
Output frequency [Hz]
0–590
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
Power card ambient trip [
°
C (
°
F)]
80 (176)
Output current [A]
Continuous (at 550 V)
659
763
763
889
889
988
988
1108
1108
1317
Intermittent (60 s overload) at 550 V
989
839
1145
978
1334
1087
1482
1219
1662
1449
Continuous (at 575/690 V)
630
730
730
850
850
945
945
1060
1060
1260
Intermittent (60 s overload) at
575/690 V
945
803
1095
935
1275
1040
1418
1166
1590
1590
Continuous (at 550 V) [kVA]
628
727
727
847
847
941
941
1056
1056
1255
Continuous (at 575 V) [kVA]
627
727
727
847
847
941
941
1056
1056
1255
Continuous (at 690 V) [kVA]
753
872
872
1016
1016
1129
1129
1267
1267
1506
Input current [A]
Continuous (at 550 V)
642
743
743
866
866
962
1079
1079
1079
1282
Continuous (at 575 V)
613
711
711
828
828
920
1032
1032
1032
1227
Continuous (at 690 V)
613
711
711
828
828
920
1032
1032
1032
1227
Power losses [W]
Drive modules at 600 V
7469
8683
8668
10166
10163
11406
11292
12852
12835
15762
Drive modules at 690 V
7381
8559
8555
9996
9987
11188
11077
12580
12551
15358
AC busbars at 575 V
637
644
644
653
653
661
661
672
672
695
DC busbars during regeneration
198
198
208
208
218
218
231
231
256
256
Maximum cable size [mm
2
(mcm)]
Mains
1)
4x120 (250)
6x120 (250)
8x120 (250)
Motor
4x120 (250)
6x120 (250)
8x120 (250)
Brake
8x70 (2/0)
8x95 (3/0)
Regeneration terminals
4x150 (300)
6x120 (250)
6x150 (300)
8x120 (250)
Maximum external mains fuses
6-pulse configuration
700 V, 1600 A
700 V, 2000 A
12-pulse configuration
700 V, 900 A
700 V, 1500 A
Table 7.14 FC 302, 525–690 V AC Mains Supply (4-module System)
1) For 12-pulse units, the cables between the star and delta terminals must be equal in number and length.
Specifications
User Guide
MG37L202
Danfoss A/S © 08/2017 All rights reserved.
67
7
7