![Danfoss VLT HVAC Drive FC 102 Скачать руководство пользователя страница 61](http://html1.mh-extra.com/html/danfoss/vlt-hvac-drive-fc-102/vlt-hvac-drive-fc-102_user-manual_3412752061.webp)
Power range
N560
N630
N710
N800
N1M0
Drive modules
4
4
4
4
4
Rectifier configuration
6-pulse/12-pulse
High/normal load
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at 400 V [kW]
500
560
560
630
630
710
710
800
800
1000
Typical shaft output at 460 V [hp]
650
750
750
900
900
1000
1000
1200
1200
1350
Protection rating
IP00
Efficiency
0.98
Output frequency [Hz]
0–590
Heat sink overtemperature trip
[
°
C (
°
F)]
110 (230)
Power card ambient trip [
°
C (
°
F)]
80 (176)
Output current [A]
Continuous (at 400 V)
880
990
990
1120
1120
1260
1260
1460
1460
1720
Intermittent (60 s overload) at 400 V
1320
1089
1485
1232
1680
1386
1890
1606
2190
1892
Continuous (at 460/500 V)
780
890
890
1050
1050
1160
1160
1380
1380
1530
Intermittent (60 s overload) at
460/500 V
1170
979
1335
1155
1575
1276
1740
1518
2070
1683
Continuous (at 400 V) [kVA]
610
686
686
776
776
873
873
1012
1012
1192
Continuous (at 460 V) [kVA]
621
709
709
837
837
924
924
1100
1100
1219
Continuous (at 500 V) [kVA]
675
771
771
909
909
1005
1005
1195
1195
1325
Input current [A]
Continuous (at 400 V)
857
964
964
1090
1090
1227
1127
1422
1422
1675
Continuous (at 460 V)
759
867
867
1022
1022
1129
1129
1344
1344
1490
Power losses [W]
Drive modules at 400 V
7713
8810
8918
10199
10181
11632
11390
13253
13479
16463
Drive modules at 460 V
6641
7628
7855
9324
9316
10375
12391
12391
12376
13958
AC busbars at 400 V
655
665
665
680
680
695
695
722
722
762
AC busbars at 460 V
647
656
656
671
671
683
683
710
710
732
DC busbars during regeneration
218
218
232
232
250
250
276
276
318
318
Maximum cable size [mm
2
(mcm)]
Mains
1)
4x185 (350)
8x125 (250)
Motor
4x185 (350)
8x125 (250)
Brake
8x70 (2/0)
8x95 (3/0)
Regeneration terminals
6x125 (250)
8x125 (250)
8x150 (300)
10x150 (300)
Maximum external mains fuses
6-pulse configuration
600 V, 1600 A
600 V, 2000 A
600 V, 2500 A
12-pulse configuration
600 V, 900 A
600 V, 1500 A
Table 7.6 FC 202, 380–480 V AC Mains Supply (4-module System)
1) For 12-pulse units, the cables between the star and delta terminals must be equal in number and length.
Specifications
User Guide
MG37L202
Danfoss A/S © 08/2017 All rights reserved.
59
7
7