Power range
N500
N560
N630
Drive modules
2
2
2
Rectifier configuration
12-pulse
High/normal load
HO
NO
HO
NO
HO
NO
Typical shaft output at 525–550 V [kW]
315
400
400
450
450
500
Typical shaft output at 575 V [hp]
400
500
500
600
600
650
Typical shaft output at 690 V [kW]
400
500
500
560
560
630
Protection rating
IP00
Efficiency
0.98
Output frequency [Hz]
0–590
Heat sink overtemperature trip [
°
C (°
°
F)]
110 (230)
Power card ambient trip [
°
C (
°
F)]
80 (176)
Output current [A]
Continuous (at 550 V)
429
523
523
596
596
630
Intermittent (60 s overload) at 550 V
644
575
785
656
894
693
Continuous (at 575/690 V)
410
500
500
570
570
630
Intermittent (60 s overload) at 575/690 V
615
550
750
627
627
693
Continuous (at 550 V) [kVA]
409
498
498
568
568
600
Continuous (at 575 V) [kVA]
408
498
598
568
568
627
Continuous (at 690 V) [kVA]
490
598
598
681
681
753
Input current [A]
Continuous (at 550 V)
413
504
504
574
574
607
Continuous (at 575 V)
395
482
482
549
549
607
Continuous (at 690 V)
395
482
482
549
549
607
Power losses [W]
Drive modules at 575 V
4892
6076
6016
6995
6941
7431
Drive modules at 690 V
4797
5951
5886
6831
6766
7638
AC busbars at 575 V
542
546
546
550
550
553
DC busbars during regeneration
91
91
186
186
191
191
Maximum cable size [mm
2
(mcm)]
Mains
1)
4x120 (250)
Motor
4x120 (250)
Brake
4x70 (2/0)
4x95 (3/0)
Regeneration terminals
4x120 (250)
Maximum external mains fuses
700 V, 630 A
Table 7.8 FC 202, 525–690 V AC Mains Supply (2-module System)
1) For 12-pulse units, the cables between the star and delta terminals must be equal in number and length.
Specifications
User Guide
MG37L202
Danfoss A/S © 08/2017 All rights reserved.
61
7
7