5.2.2 RS485 Network Connection
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1
R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
-
61
68
69
RS-485
+
130BB685.10
Function
Setting
Parameter 8-30 P
rotocol
[0] FC*
Parameter 8-31 A
ddress
1*
Parameter 8-32 B
aud Rate
9600*
*=Default value
Notes/comments:
Select protocol, address, and
baud rate in the above-
mentioned parameters.
Terminals 68 and 69 are
connected to an RS485 serial
communication circuit from an
external controller.
Table 5.3 RS485 Network Connection
5.2.3 Smart Logic Controller (SLC) Mode
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1
R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
130BB839.10
Function
Setting
Parameter 4-30
Motor Feedback
Loss Function
[1] Warning
Parameter 4-31
Motor Feedback
Speed Error
100 RPM
Parameter 4-32
Motor Feedback
Loss Timeout
5 s
Parameter 7-00 S
peed PID
Feedback Source
[2] MCB 102
Parameter 17-11
Resolution (PPR)
1024*
Parameter 13-00
SL Controller
Mode
[1] On
Parameter 13-01
Start Event
[19] Warning
Parameter 13-02
Stop Event
[44] Reset key
Parameter 13-10
Comparator
Operand
[21] Warning
no.
Parameter 13-11
Comparator
Operator
[1] ≈*
Parameter 13-12
Comparator
Value
90
Parameter 13-51
SL Controller
Event
[22]
Comparator 0
Parameter 13-52
SL Controller
Action
[32] Set
digital out A
low
Parameter 5-40 F
unction Relay
[80] SL
digital
output A
*=Default value
Notes/comments:
If the limit in the feedback monitor is exceeded,
warning 90,
Feedback monitor
is issued. The SLC monitors the warning and in
the case that it becomes true, relay 1 is triggered.
External equipment may indicate that service is required. If the
feedback error goes below the limit again within 5 s, the drive
system continues and the warning disappears. However, relay 1
is still triggered until [Reset] is pressed on the LCP.
Table 5.4 Using SLC to Set a Relay
Application Set-up Examples
VLT
®
Parallel Drive Modules
24
Danfoss A/S © 08/2017 All rights reserved.
MG37L202